Installation

Selection of the best location
Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good.
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or service
under the product.
Capacity (kBtu/h)
5/7/9
12/15/18
21/24
Minimum floor area
- The appliance shall be installed, operated and stored in a room
with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
Amin (m
)
2
600
500
400
300
200
100
0
0
1.224
(Unit: mm)
A
B
600
800
600
1000
600
1200
(for R32)
2
3
4
5
Top view
Inspection hole
(Unit: mm)
(600 x 600)
600
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
B(Min)
A(Min)
Floor standing
Wall mounted
Ceiling mounted
m (kg)
6
7
8
Installation
Control box
Air outlet
600
Air outlet
H=20 or more
Ceiling
Service Space
A
B
B
Installation Manual 9