MOUNTING AND OPERATING INSTRUCTION FOR THE
1
SPIROTOP
Applies to product types starting with AB except for ABS.
Manufacturer: Spirotech b.v. Helmond - The Netherlands
This Spirotech product is designed and manufactured according to
the Sound Engineering Practice as stated in the Pressure Equipment
Directive (97/23/EC art.3.3) adopted by the European Parliament and
the European Council in May 1997
Instruction
This instruction must be given to the end user, who should keep it.
Take into account local regulations.
Application
Fully automatic removal of air and gas from heating water, cooling
water, water/glycol mixtures and process water. Not suitable for dem-
ineralised water, drinking water, potable water and dangerous or
inflammable substances. Do not use in combination with chemical
additives.
When in doubt contact your supplier.
Pressure and temperature range
From 0 to 10 bar; from 0 to 110
wise on the product.
Installation and maintenance may only be carried out by a
competent installer.
When working on the Spirotop always make the installation pres-
sureless and let it cool down.
Installing the Spirotop
The Spirotop should be installed where trapped air is expected.
• Connecting dimension G
• Make sure that the vent valve
• If the installation is tested with compressed air, the Spirotop should
be shut off temporarily with plug R
• Take care: plug R
installation.
• Maximum allowable test pressure 15 bar.
UK
/
1
2
/
must be removed before commissioning the
1
2
C, unless explicitly indicated other-
0
Female.
is always left clear.
/
(not supplied)
1
2
.