Herunterladen Diese Seite drucken
Honeywell MORLEY-IAS MI-DCMOE Installationsanleitung

Honeywell MORLEY-IAS MI-DCMOE Installationsanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Fig./Abb. 1
1:2 DIN
1:1 M200E-SMB
Sollevare
Levantar
Anheben
Fig./Abb. 2
Fig./Abb. 3
Fig./Abb. 4
DOP-IOD080
0905
EN54-17: 2005
21
EN54-18: 2005
M200-501-00
22 mm
60°C
-20°C
2
1
Rotate
Plug
Ruotare
Inserire
Girar
Conectar
Drehen
Einhaken
Clip / Agganciare
3
Acoplar / Einrasten
3
1
Lift
Push down
Premere
Precionar
hacia abajo
Runterdrücken
2
Rotate / Ruotare
Girar / Drehen
MI-DCMOE
MI-DCMOE
(i)
+
(iii)
Fig./Abb. 5
Honeywell Morley-IAS
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
Honeywell Morley-IAS, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK
MI-DCMOE
EN
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The Morley series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices. The MI-DCMOE
is an output module that allows the control of auxiliary devices such as fire shutters
or sounders.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module is
polled. When the control panel switches the relay to the energised state the LED can
be set to continuous green.
SPECIFICATIONS
Operating Voltage Range:
Maximum Standby Current
LED Current (Red):
LED Current (Yellow):
Isolator features:
Humidity:
Maximum Wire Gauge
INSTALLATION
Note: These modules must only be connected to control panels using compatible
proprietary analogue addressable communication protocols for monitoring and control.
Morley series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in Figure 1:2.
Wiring to all series Morley modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 4). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module. (Note: The number of addresses
available will be dependent on panel capability, check the panel documentation for
information on this.)
Short Circuit Isolators
All Morley series modules are provided with short circuit monitoring and isolators on
the intelligent loop. If required the isolators may be wired out of the loop to facilitate
the use of the modules on high current loaded loops, for example if sounders are
used. To achieve this, the loop out positive should be wired to terminal 5 rather than
terminal 2. See the relevant wiring diagram for details.
MI-DCMOE WIRING
The MI-DCMOE can be wired for either Supervised (Figure 2) or Non-Supervised
(Figure 3) operation respectively.
MI-DCMOE Single Output Module with Supervised Output
When the module is used in supervised mode and power is supplied to the module,
a switched negative input on terminal 12 can be used to signal an external fault
condition, such as a power supply fault. Loss of power is also supervised in this mode
such that if the supply voltage falls below 7V a fault indication is achievable. Note that
the use of this fault mode is dependant on panel software. Please contact the panel
(ii)
manufacturer for further details.
PSU monitoring is not available when the module switches the output to Alarm.
Wire as follows (see Figure 2):
a: T1 Loop Output -. b: T2 Loop Output +. c: T3 Loop Input -. d: T4 Loop Input +
e: T5 Loop Output +. If short circuit isolation is not required, loop output+ should be
wired to terminal 5 and not 2. Terminal 5 is internally connected to terminal 4.
f: To enable output circuit supervision, the link supplied must be fitted across
terminals 6 and 7, and the load must be polarised.
INSTALLATION INSTRUCTIONS
FOR THE MI-DCMOE OUTPUT MODULE
15 to 32VDC (Min 16.5VDC for LED operation)
160 µA - No Communication
1.5 mA
5.5 mA
see S00-7100
5% to 95% relative humidity (non-condensing)
2.5 mm²
CAUTION
CAUTION
Electrostatic Sensitive Device
Observe precautions when handling and making connections
I56-4407-001

Werbung

loading

Inhaltszusammenfassung für Honeywell MORLEY-IAS MI-DCMOE

  • Seite 1 To enable output circuit supervision, the link supplied must be fitted across Pittway Tecnologica S.r.l EN54-17: 2005 terminals 6 and 7, and the load must be polarised. Via Caboto 19/3 EN54-18: 2005 34147 Trieste, Italy M200-501-00 Honeywell Morley-IAS, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK I56-4407-001...
  • Seite 2 5 anziché al morsetto 2. CABLAGGIO DEL MODELLO MI-DCMOE È possibile cablare il modello MI-DCMOE affinché funzioni in modalità di Supervisione (Figura 2) o di Non Supervisione (Figura 3). M200-501-00 Honeywell Morley-IAS, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK I56-4407-001...
  • Seite 3 El MI-DCMOE se puede conectar para que funcione Con Supervisión (Figura 2) o Sin Supervisión (Figura 3). PRECAUCIÓN Equipo sensible a la electricidad estática Tome las precauciones necesarias al manejar el equipo y hacer las conexiones Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19 08911 Badalona (Barcelona), Espana M200-501-00 I56-4407-001...
  • Seite 4 Ausgang "Ringleitung+" direkt an Klemme 5 anstatt an Klemme 2 angeschlossen werden. Klemme 5 ist intern direkt mit Klemme 4 verbunden. f: Zur Aktivierung der Ausgangsüberwachung muss die mitgelieferte Verbindung zwischen Klemme 6 und 7 und eine gepolte Last angeschlossen werden. Honeywell Morley-IAS, Stadionring 32, 40878 Ratingen,...