Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Datas - Kingspan Rm Basic Technische Information Und Bedienungsanleitung

Riegelmotor
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Locking motor RM Basic

Technical datas

The motors and electrical control equipment are to be operated exclusively with the components authorised by the
manufacturer.
Electrical properties
Nominal voltage:
Allowed voltage range:
Allowed ripple of nominal voltage:
Nominal current:
Starting current:
Current draw at cut-out torque:
Current draw after cut-off (standby):
Cut-off:
Cut-off in each position:
Mechanical properties
Stroke lengths:
Force:
Nominal clamping force:
Speed:
Dimensions:
Weight:
Circuit connections and operation
Connections:
Break time when change of driving direction: min. 100 ms
Start-up time:
Service live:
Permanent voltage:
Maintenance:
Installation and ambient conditions
Nominal temperature:
Ambient operating temperature:
Suitable for SHE:
Suitable for external mounting:
Protection degree:
Authorisations and certifications
CE compliant:
Class of protection:
Type tested:
18
24 V DC
-20 % / +50 % of the nominal voltage
20 %
approx 0.8 A at 600 N
approx. 1.2 A at 1200 N
3 A
1.1 A at 600 N
1.8 A at 1200 N
60 mA at single operation
(observe the current of the connected chain motors during system
operation)
with integrated power cut-off
yes
18 mm (special stroke to 36 mm on request)
600 N or 1200 N
3000 N
approx. 6 s
see page 11 technical measures
approx 1 kg (without fittings)
2 x 0.75 mm² silicon cable, approx. 3 m from cable opening end, 5-core
screw terminal for maximum cable cross-section of 1 mm²,
connection cable included in delivery
30 % ED according to 10 min,
3 min (ED/ON), 7 min (AD/OFF)
> 10,000 ventilation cycles at nominal load
suitable
see page 12 maintenance works
20 °C
-10 °C to +60 °C
yes
no
IP 20 according to DIN EN 60529
in accordance with EMV directive 2004/108/EG and the low voltage
directive 2006/95/EG
class III in accordance with DIN EN 61140 (VDE 0140-1)
-/-
06/24999480
Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rm basic 1200 n

Inhaltsverzeichnis