XMS Handbook
Environmental Specifications:
Description
Use
Temperature
Humidity
Altitude
Pressure
Orientation
Material Group
Pollution Degree
Overvoltage Category
Class
Weight
IP Rating
* 5000m (54kPa) for 60950-1 only, 4000m (61.64kPa) for 60601-1 3
Edition
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth: 2.68kVdc
Primary mains circuits to secondary: 6.863kVdc*
Secondary circuits to earth: 2.13KVdc
*Important Note: This test is not possible with Y capacitors fitted to the unit as damage to these
capacitors may occur.
Routine Dielectric Strength testing is carried out as follows:
Class I Products: Primary mains circuit to Secondary circuits and earth shorted together 2.25kVdc to 2.35kVdc.
Secondary circuits to earth 2.25kVdc to 2.35kVdc.
Class II products: Primary mains circuit to Secondary circuits 4.25kVdc to 4.35kVdc.
Safety approvals
UL60950-1 and CSA22.2 No.60950-1 - UL Recognised. C-UL for Canada.
IEC / EN60950-1 - CE mark.
IEC/EN60950-1 and IEC/EN60601-1 - CB Report and Certificate.
CE marking when applied to any XMS product indicates compliance with the Low Voltage Directive
in that it complies with EN60950-1, and with the ROHS Directive.
UL/CSA 60601-1 - UL + C -UL approval
Fusing: Internal fuses (F1): dual fuses in the L and N line or single fuse in the Live/+ Line, F10AH or F8AH, 250V,
5x20mm.
Symbols:
AC
EARTH
Caution
Operation
Indoor
0°C to +50°C
5 - 95% RH, non-condensing
-200m to 5000m*
54kPa (5000m)* - 106kPa
The unit may be mounted in any orientation except
inverted (mounted on its top)
N – Neutral
L – Live
Warning: Dangerous Voltage
IIIb
2
II
I
1 kg max
IPX0
rd
Edition and 3000m (70kPa) for 60601-1 2
Page 14 of 24
Storage & Transportation
-
-40°C to +70°C
5 - 95% RH, non-condensing
-200m - 5000m
54kPa - 106kPa
ALL
260217 issue 10, May 2018
nd