PARAMETER SELECTION SEQUENCE

1 K1, K2 and K3 shunts positioning
Position the shunts as follows (before modification, switch off the card):
K3 OFF
K3 ON
2 Selection of the flow direction of the valve
2.1 Normal flow direction (by default)
G
2.2 Inverse flow direction
R
3 Selection of the type of input control signal
3.1 Voltage control signal 0-10V
R
3.2 Current control signal 0-20mA
R
3.3 Current control signal 4-20mA (by default)
R
4 Learning mode
G
R
R
R
G
G
NORMAL OPERATING MODE
G
In the case of an over torque, the motor stops and the 2 LEDS lights then together to indicate the
action of the torque limiter. To re-start it, you must either reverse the sense of rotation, either switch
G
R
the power off and on.
DSBA3200 • Rév. 30/09/2020
Setpoint
signal
0-10V
0-10V
0-10V
0-20mA
0-20mA
0-20mA
4-20mA
4-20mA
4-20mA
Press the OPEN button and apply the operating voltage to the card while keeping this button

pressed.
The green LED lights up. Release the OPEN button.

Disconnect the card.

Press the CLOSE button and apply the operating voltage to the card while keeping this button

pressed.
The red LED lights up. Release the CLOSE button.

Disconnect the card.

Press the MEM button and apply the operating voltage to the card while keeping this button

pressed.

The red LED will light up 3 times. Release this button.

Disconnect the card.

Press the MEM and OPEN buttons and apply the operating voltage to the card while keeping
these buttons pressed.
The red LED will light up 3 times. Release these buttons.

Disconnect the card.

Press the MEM and CLOSE buttons and apply the operating voltage to the card while keeping

these buttons pressed.
The red LED will light up 3 times. Release these buttons.

Disconnect the card.

Press the OPEN and CLOSE buttons and apply the operating voltage to the card while

keeping these buttons pressed.
The 2 LEDs will light up. Release these buttons and the 2 LEDs will run out. The card is now in

the learning mode.
Press the CLOSE button to put the valve in its closed position. The red LED will light up.

Store this selected closed position by pushing MEM + CLOSE, the red LED will light up 2

times as a confirmation of acknowledgement.
Press the OPEN button to put the valve in its open position. The green LED will light up.

Store this selected open position by pushing MEM + OPEN, the green LED will light up 2

times as a confirmation of acknowledgement.
Now, the positions selected have been stored. Disconnect the card.

Apply the operating voltage to the card. The green LED will light up 3 times.

Under normal operating conditions, the green LED will light up when the drive motor opens the

valve, and the red LED will light up when the drive motor closes it.

If both LEDs remain ran out, it means that the drive motor has not been triggered.
Feedback
Shunt K1
signal
A
B
0-10V
ON OFF
0-20mA
ON OFF
4-20mA
ON OFF
0-10V
OFF
ON
0-20mA
OFF
ON OFF
4-20mA
OFF
ON OFF
0-10v
OFF
ON
0-20mA
OFF
ON OFF
4-20mA
OFF
ON OFF
Shunt K2
Shunt K3
A
B
ON OFF
OFF
OFF
ON
OFF
OFF
ON
ON
ON OFF
OFF
ON
OFF
ON
ON
ON OFF
OFF
ON
OFF
ON
ON