Various control types (control signal on terminals N°15 and N°16)
On request, our cards can be set in factory. The consign and the feedback signal can have different forms (current or voltage).
Without any information from the customer, the cards are set for current 4-20mA (control + feedback signal)
Control in modes 0-10V and 0-20mA
In case of outside event, absence of control signal (accidental wires cut for example) but in presence of power, the actuator
will travel to defined position (open or closed valve).
In standard our actuators will close themselves in absence of control signal but there are other possibilities on request.
Control in mode 4-20mA
In case of outside event, absence of control signal (accidental wires cut for example) but in presence of power, the actuator
will stay in its position.
In the both cases, when the control signal is restored, the actuator reach automatically the position corresponding to control
signal value.
P6 positioning electronic board (0-20mA / 4-20mA / 0-10V)
N
L
G
H
B
C
A
M
Actionneur déjà préréglé en usine
P6 positioning board wiring (input and output signal)
In order to avoid electromagnetic perturbations, it is compulsory to use shielded cables (cables longer than 3m).
Unscrew the gland and pass the cable.
Connect the setpoint signal between terminals 15 and 16.
Terminal 15 is the negative polarity (-) and terminal 16 is the positive polarity (+).
Connect the feedback signal between terminals 13 and 14.
Terminal 13 is the positive polarity (+) and terminal 14 is the negative polarity (-).
Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
Factory setting : by default, 4-20mA input and output signals with normal rotation direction.
To proceed to a new setting of the card : please see page 27, "Parameter selection sequence".
To check the proper operation of the card : please see page 27, "Normal operating mode".
DSBA3200 • Rév. 30/09/2020
REP
DESIGNATION
D
A
24V AC/DC power supply terminal trip
E
B
Setpoint signal terminal trip
C
Feedback signal terminal trip
F
D
Adjustment button MEM
E
Adjustment button CLOSE
F
Adjustment button OPEN
G
K1 shunt
J
H
K2 shunt
I
K3 shunt
K
J
Green and red LEDs
I
K
Yellow LED : power supply indication
L
Potentiometer
M
Motor connexion
N
Heating resistor connector