7. Configuration
Control Output 1 (OUT1) proportional band
P
Input of the proportional band for control output 1.
By entering the value 0 or 0.0, the controller is configured as an
0 ... 1,000 °C (2,000 °F), 0.0 ... 999.9 °C (°F) or 0.0 ... 100.0 %
Control output 2 (OUT2) proportional band
p_b
Input of the proportional band for control output 2.
Control mode
Not available if the option 2 control output [DT2] is not present, or if
mode is set on control output 1.
0.0 ... 10.0 (Multiplier for proportional band for control output 1)
Integral time
1
Input of the integral time for the control.
Entering the value 0 deactivates this function (⇒ control mode PD).
Not available with
Setting range: 0 ... 1,000 seconds
Derivative time
d
Input of the derivative time for the control.
Entering the value 0 deactivates this function (⇒ control mode PI).
Not available with
Setting range: 0 ... 300 seconds
ARW (Anti-reset windup) parameter
A
Input of the paramter for the anti-reset-windup
Only available with PID control mode
Setting range: 0 ... 100 %
Control output 1 (OUT1) cycle time
c
Input of the cycle time for control output 1
This function is not available with
signal control output.
With relay control output, shortening the cycle time leads to more-frequent
switching of the output relay, which increases the wear and shortens the service
life.
Setting range: 1 ... 120 seconds
Control output 2 (OUT2) cycle time
c_B
Input of the cycle time for control output 2
Not available if the option 2, control output [DT2] is not present, or if
mode is set on control output 2.
Setting range: 1 ... 120 seconds
Alarm value alarm 1 (A1)
A1
Input of the switching value for alarm output 1 (A1).
Entering the value 0 or 0.0 deactivates the alarm (with the exception of the alarm
types process high alarm and process low alarm)
Not available when no alarm is selected for alarm type alarm 1 (A1).
Setting range: see table "A1, A2 setting ranges"
Alarm value alarm 2 (A2)
A2
Input of the switching value for alarm output 2 (A2).
Entering the value 0 or 0.0 deactivates the alarm (with the exception of the alarm
types process high alarm and process low alarm)
Not available if the options alarm output 2 [2AS] or [2AL] are not present, or no
alarm is selected for the alarm type alarm 2 (A2).
Setting range and factory setting are identical with those from alarm 1 (see table
"A1, A2 setting ranges").
WIKA operating instructions model CS4S
/
with input of the value 0 or 0.0
ON
OFF
/
control mode for control output 1
ON
OFF
/
control mode for control output 1
ON
OFF
(Values > 50 %: additional damping to reduce overshoot
Values < 50 %: generate a steeper rise with "Start up")
/
ON
OFF
/
ON
OFF
control mode nor with analogue current
10 °C
controller.
1.0
/
control
ON
OFF
200 s
50 s
50 %
30 s (relay
control output)
or 3 s (logic
level control
output)
Logikpegel)
3 s
/
control
ON
OFF
0 °C
0 °C
GB
23