Using Weather-Dependent Curves - Daikin Altherma 3 H HT F+W Betriebsanleitung

Vorschau ausblenden Andere Handbücher für Altherma 3 H HT F+W:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
a
b
Y4
Y3
Y2
Y1
X1
Item
a
WD curve before changes.
b
WD curve after changes (as example):
▪ When
slope
is
temperature at X1 is unequally higher than the
preferred temperature at X2.
▪ When
offset
is
temperature at X1 is equally higher as the preferred
temperature at X2.
c
Slope
d
Offset
e
Selected weather dependent zone:
: Main zone or additional zone heating
: Main zone or additional zone cooling
: Domestic hot water
X1, X2
Examples of outdoor ambient temperature
Y1, Y2,
Examples of desired tank temperature or leaving water
Y3, Y4
temperature. The icon corresponds to the heat emitter
for that zone:
: Underfloor heating
: Fan coil unit
: Radiator
: Domestic hot water tank
Possible actions on this screen
Select slope or offset.
Increase or decrease the slope/offset.
When slope is selected: set slope and go to offset.
When offset is selected: set offset.
Confirm changes and return to the submenu.
4.9.4

Using weather-dependent curves

Configure weather-dependent curves as following:
To define the setpoint mode
To use the weather-dependent curve, you need to define the correct
setpoint mode:
Go to setpoint mode ...
Main zone – Heating
[2.4] Main zone > Setpoint
mode
Main zone – Cooling
[2.4] Main zone > Setpoint
mode
ETVH/X16S18+23DA6V+9W(G) + ETBH/X16DF6V+9W
Daikin Altherma 3 H HT F+W
4P586455-1C – 2020.10
c
e
d
X2
Description
changed,
the
new
preferred
changed,
the
new
preferred
Set the setpoint mode to ...
WD heating, fixed cooling
OR Weather dependent
Weather dependent
Go to setpoint mode ...
Additional zone – Heating
[3.4] Additional zone >
Setpoint mode
Additional zone – Cooling
[3.4] Additional zone >
Setpoint mode
Tank
[5.B] Tank > Setpoint mode
To change the type of weather-dependent curve
To change the type for all zones (main + additional) and for the tank,
go to [2.E] Main zone > WD curve type.
Viewing which type is selected is also possible via:
▪ [3.C] Additional zone > WD curve type
▪ [5.E] Tank > WD curve type
Restriction: Only available to installers.
To change the weather-dependent curve
Zone
Main zone – Heating
Main zone – Cooling
Additional zone – Heating
Additional zone – Cooling
Tank
INFORMATION
Maximum and minimum setpoints
You cannot configure the curve with temperatures that are
higher or lower than the set maximum and minimum
setpoints for that zone or for the tank. When the maximum
or minimum setpoint is reached, the curve flattens out.
To fine-tune the weather-dependent curve: slope-offset curve
The following table describes how to fine-tune the weather-
dependent curve of a zone or tank:
You feel ...
At regular outdoor
At cold outdoor
temperatures ...
temperatures ...
OK
Cold
OK
Hot
Cold
OK
Cold
Cold
Cold
Hot
Hot
OK
Hot
Cold
Hot
Hot
To fine-tune the weather-dependent curve: 2-points curve
The following table describes how to fine-tune the weather-
dependent curve of a zone or tank:
4 Operation
Set the setpoint mode to ...
WD heating, fixed cooling
OR Weather dependent
Weather dependent
Restriction: Only available to
installers.
Weather dependent
Go to ...
[2.5] Main zone > Heating WD
curve
[2.6] Main zone > Cooling WD
curve
[3.5] Additional zone >
Heating WD curve
[3.6] Additional zone >
Cooling WD curve
Restriction: Only available to
installers.
[5.C] Tank > WD curve
Fine-tune with slope and
offset:
Slope
Offset
Operation manual
17