Procedure
Whenthe
Action/Description
displayshows
Put the instrument in setup mode and scroll through the main menu
CALOut_n
Press ì or Å
Press PGM to select output calibration
CAlOut_y
Connect the multimeter to measure the output level, then press PGM
Out_LO_=
Press PGM
Measure the output signal
4. 0 0
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press PGM
Press PGM
Out_HI_=
Press PGM
Measure the output signal
20. 0 0
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press PGM
Continue with the setup sequence.
Save
Note: Do not remove the power while the save message is on display.
InputCalibration
Terminal Connections for Input calibration are:
CalibrationStage
mA/Voltage Signal Source
Signaltype
Signal +
Signal –
Terminal