1. Components
Cable for night operation or peak-cut control (5-core
cable with yellow connector)
Compressor output cable (2-core cable with blue
connector)
Installation Manual (this manual)
Application

2. Connecting the Cables

<System diagram>
EN
Outdoor unit
cycle control P.C. board
Connect the cables firmly to the cycle control P.C. board of the outdoor unit so that they will not be disconnected from
respective connectors.
Connect the cables carefully so that they are not caught by mechanical parts.
If any of the cables is caught, overheating or fire may be caused.
2-EN
Component
• Peak-cut control ...........................Saves the power of the outdoor unit by the external peak-cut signal to
.....................................................The power saving can be switched to three levels: 75%, 50%, and
• Night operation .............................Reduces the capacity of the air conditioner by the input signal from a
• Compressor output.......................Turns on the no-voltage contact output while the compressor is
1
1
2
2
CN610
3
3
(Yellow)
4
4
5
5
6
1
1
CN704
(Blue)
3
3
Q'ty
1
1
1
suppress temporary peak power dissipation.
operation stop.
commercially available timer (procured locally) regardless of the
outside air temperature or load to reduce operating noise.
operating.
(Procured locally)
Timer or switch (commercially available)
White
Night operation
Black
Yellow
Operation stop
Orange
Red
(Procured locally)
Red
Power supply
White
L
RUN lamp
Note) Indication relay contact capacity
AC250V 10mA~1A
DC30V 10mA~1A
Non-inductive load
DC5V 10mA~1A
• Be sure to connect a load such as a lamp (L).
• When connecting an inductive load such as a relay coil, insert a surge-killer
capacitor and resistor (for AC circuit) or a surge suppressor diode (for DC circuit)
into the bypass circuit.
CAUTION
– 2 –
Remarks
Use these cables as required.
50%
Peak-cut
75%