Setting when connecting
indoor units to FS unit
Caution to connection of indoor
unit
When connecting the indoor units to FS unit, it is
necessary to set up the CODE No..
Be sure to set up the CODE No. after set up of address.
• When connecting the indoor units to FS unit, group
control and individual control are available.
[ 0E ] : Group setting
0 : Individual (Factory default)
1 : Group
[ 14 ] :
Group address setting
0 : Individual (Factory default)
1 : Header
2 : Follower
[ FE ] : Branching system address (1~64)
• Should not be duplicate in one system
• Factory default : 99
[ FD ] : Priority operation mode
0 : Heating prioritized (Factory default)
1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in
one branching)
FS unit
Piping
Indoor unit
Remote controller
Group control
EN-57
How to set up CODE No. [ 0E ]
It is necessary to set up in case of the group control.
.
2
5
1
Push and hold the
,
, and
buttons
at the same time for more than 4 seconds.
is displayed in the UNIT No. window.
• In this time, the fans of all the indoor units in
the group control start the fan operation.
2
Using the set temperature buttons
, select the CODE No. "
".
3
Change SET DATA to "
" by the timer
buttons
/
.
4
Push
button.
5
Push
button. Then the setup finished.
How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit
or one group, it is necessary to set up.
• As for both single port type and multi port type, set
up CODE No. "FE" in one branching within the range
of 1~64.
This CODE No. should not be duplicate in one
system.
How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit
or one group, it is necessary to set up.
0 : Heating prioritized (Factory default)
1 : Cooling prioritized
29
Case that FE/FD setting is not necessary
FS unit
Piping
Remote controller
3
Group control
4
1
/
Case that FE/FD setting is necessary
FS unit
Piping
Indoor unit
Remote controller
Group control
FS unit
Remote
controller
Group control
Indoor unit
Group control
Piping
Indoor unit
EN-58