Technical data
Standards and operating conditions

Electrical supply conditions

EMC data

Actuation on public supply systems
Implement measures to limit the radio
interference to be expected:
< 1 kW: with mains choke
> 1 kW at mains current ≤ 16 A: without
additional measures
Mains current > 16 A: with mains choke or
mains filter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
Noise emission
Category C2
Noise immunity
Meets requirement in compliance with

Environmental conditions

Climate
1K3 ( -30 °C ... +60 °C)
1K3 ( -30 °C ... +40 °C)
2K3 ( -30 °C ... +70 °C)
3K3 ( -30 °C ... +40 °C)
In the case of very low-temperature appli-
cations without condensation
Site altitude
0 ... 1000 m a.m.s.l.
1000 ... 4000 m a.m.s.l.
Degree of pollution
Degree of pollution 2
Vibration resistance
2M2
3M4
Vibration severity
A
Electrical supply conditions
Possibility of connection to different types of mains power supply enables worldwide use.
The following is supported:
• 3-phase mains connection 400 V
• 3-phase mains connection 480 V
Type of mains power supply
TT
TN
70
The machine or plant manufacturer is responsible for com-
pliance with the requirements for the machine/plant!
EN 61000-3-2
EN 61000-3-12
RSCE: short-circuit power ratio at the connection point of
the machine/plant to the public network.
EN 61800-3
EN 61800-3
EN 60721-3-1
Storage, < 3 months
EN 60721-3-1
Storage, > 3 months
EN 60721-3-2
Transport
EN 60721-3-3
operation
Without power reduction
Reduce rated output current by 5 %/1000 m
EN 61800-5-1
EN 60721-3-2
Transport
EN 60721-3-3
operation
EN 60034-14
Mains power supplies with earthed start point
Voltage against earth: max. 300 V