G
®
AERASGARD
RCO
Maintenance-free room sensor AERASGARD
on lid, for determining the CO
signal of 0 -10 V.
Maintenance-free room sensor AERASGARD
plastic housing with snap-on lid, optional with traffic light indicator (five coloured LEDs), for determining the CO
(0...2000 ppm/0...5000 ppm). The measuring transducer converts the measured values into a standard signal of 0 -10 V or 4...20 mA (switchable).
The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables
energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The CO
measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for
2
standard applications such as monitoring residential rooms and conference rooms.
TECHNICAL DATA
Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Warm up time:
Response time:
Electrical connection:
Housing:
Dimensions:
Installation:
Protection class:
Protection type:
Standards:
Optional:
®
AERASGARD
RCO
- SD Room CO
2
AERASGARD
®
RCO
- W
2
Type ⁄ WG02
Measuring Range
CO
2
RCO
- SD
(fixed)
2
R C O 2 - S D - U
0...2000 ppm
RCO
- W
(switchable)
2
R C O 2 -W
0...2000 ppm ⁄ 0...5000 ppm 0 -10 V ⁄ 4...20 mA
RCO2-W VA
0...2000 ppm ⁄ 0...5000 ppm 0 -10 V ⁄ 4...20 mA
RCO2-W DISPLAY
0...2000 ppm ⁄ 0...5000 ppm 0 -10 V ⁄ 4...20 mA
RCO
- W - A
(switchable)
2
R C O 2 -W- A
0...2000 ppm ⁄ 0...5000 ppm 0 -10 V ⁄ 4...20 mA
A = with "traffic light" (five coloured LEDs) for displaying the CO
Note:
This unit must not be used as safety-relevant device!
- W ⁄ RCO
- SD
2
2
®
RCO
- SD with active output, automatic calibration (fixed), in an elegant plastic housing with snap-
2
content of the air (0...2000 ppm). The measuring transducer converts the measured values into a standard
2
®
RCO
- W with active/switching output, automatic calibration (can be deactivated), in an elegant
2
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical;
< 2.9 VA ⁄ 24 V AC typical;
peak current 200 mA
Optical NDIR sensor (non-dispersive infra-red technology), with manual calibration (via zero button),
RCO
- SD
with automatic calibration (fixed)
2
RCO
-W
with automatic calibration (can be deactivated via DIP switches)
2
RCO
- SD
0...2000 ppm (fixed)
2
RCO
- W
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
2
RCO
- SD
0 -10 V (fixed)
2
RCO
- W
0 -10 V or 4...20 mA, working resistance < 800 Ω
2
(selectable via DIP switches), with offset potentiometer (± 10 % of the measuring range)
RCO
- SD
without changeover contact
2
RCO
- W
with potential-free changeover contact (24 V / 1 A)
2
typically ± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
< 2 minutes
2
0.14 - 1.5 mm
, via screw terminals
plastic, material ABS, colour pure white (similar to RAL 9010), stainless steel housing optional V2A (1.4301)
85 x 85 x 27 mm (Baldur 1)
100 x 100 x 25 mm (stainless steel)
wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting on vertically or horizontally
installed in-wall flush boxes for cable entry from the back, with predetermined breaking point for on-wall
cable entry from top ⁄ bottom in case of plain on-wall installation
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive 2014 ⁄ 35 ⁄ EU
with traffic light indicator (five coloured LEDs, see table) for displaying the CO
with display (see AERASGARD
sensor and measuring transducer, Standard
2
Room CO
sensor and measuring transducer, Premium
2
Output
CO
2
(fixed)
0 -10 V
(switchable)
(switchable)
®
RFTM-LQ-CO
) for displaying the actual CO
2
Equipment
–
Changeover contact
Changeover contact, stainless steel housing
Changeover contact, display
Changeover contact, LEDs
concentration.
2
Rev. 2020 - V33
content of the air
2
concentration
2
content in ppm
2
Display Item No.
(Baldur 1)
1501-61A0-1001-200
1501- 61A 0- 7301-200
1501- 61A 0- 7301-205
■
see RFTM-LQ-CO
2
with traffic light
1501- 61A 0- 7331-200