re g i ste r de s crip tion
INSTrUMENT GENErAL SETUP
Digital output 1 mode
Digital output 1 parameter
Digital output 1 setup according to the mode:
Alarm (AL): Threshold referred to the set parameter
Pulse (PULS): Pulse weight numerical value
Digital output 1 setup according to the mode:
Alarm (AL): Hysteresis value
Pulse (PULS): Pulse value format
Digital output 2 mode
Digital output 2 parameter
Digital output 2 setup according to the mode:
Alarm (AL): Threshold referred to the set parameter
Pulse (PULS): Pulse weight numerical value
Digital output 2 setup according to the mode:
Alarm (AL): Hysteresis value
Pulse (PULS): Pulse value format
ETHERNET set default
Restore the ETHERNET settings to the default values
(IP, account username&password)
Available only for instrument with ETHErNET port.
72
INTE G E r
F. code
register
(Hex)
words
(Hex)
03 / 04 / 10
204C
2
03 / 04 / 10
204E
2
03 / 04 / 10
2050
4
03 / 04 / 10
2054
2
03 / 04 / 10
2056
2
03 / 04 / 10
2058
2
03 / 04 / 10
205A
4
03 / 04 / 10
205E
2
10
2074
2
P ro gr a mmabl e dat a
$00=disabled
$01=alarm (high threshold)
$02=alarm (low threshold)
$03=pulse
Refer to the "Parameter codes" table
In Alarm mode:
$0001... full scale value of the set
parameter. The measuring unit changes
according to the set parameter. The
value is always expressed with the milli
(m) coefficient:
e.g. $38270=230000mV=230V
For Phase sequence parameter, set $0000.
In Pulse mode:
$0001...$270F (1...9999)
In Alarm mode:
$00...$32 (0...50%)
For Phase sequence parameter, set $00.
In Pulse mode:
$01=X.XXX kWh, VAh, varh / pulse
$02=XX.XX kWh, VAh, varh / pulse
$03=XXX.X kWh, VAh, varh / pulse
$04=X.XXX MWh, VAh, varh / pulse
$05=XX.XX MWh, VAh, varh / pulse
$06=XXX.X MWh, VAh, varh / pulse
$07=XXXX MWh, VAh, varh / pulse
$00=disabled
$01=alarm (high threshold)
$02=alarm (low threshold)
$03=pulse
Refer to the "Parameter codes" table
In Alarm mode:
$0001... full scale value of the set
parameter. The measuring unit changes
according to the set parameter. The
value is always expressed with the milli
(m) coefficient:
e.g. $38270=230000mV=230V
For Phase sequence parameter, set $0000.
In Pulse mode:
$0001...$270F (1...9999)
In Alarm mode:
$00...$32 (0...50%)
For Phase sequence parameter, set $00.
In Pulse mode:
$01=X.XXX kWh, VAh, varh / pulse
$02=XX.XX kWh, VAh, varh / pulse
$03=XXX.X kWh, VAh, varh / pulse
$04=X.XXX MWh, VAh, varh / pulse
$05=XX.XX MWh, VAh, varh / pulse
$06=XXX.X MWh, VAh, varh / pulse
$07=XXXX MWh, VAh, varh / pulse
$AAAA$AAAA=ETHERNET set default
MODBUS rTU/ASCII, TCP