Param e ter
MAXIMUM VALUES
V1
• Phase 1-N voltage MAX
MAX
V2
• Phase 2-N voltage MAX
MAX
V3
• Phase 3-N voltage MAX
MAX
V12
• Line 12 voltage MAX
MAX
V23
• Line 23 voltage MAX
MAX
V31
• Line 31 voltage MAX
MAX
V∑
• System voltage MAX
MAX
A1
• Phase 1 current MAX
MAX
A2
• Phase 2 current MAX
MAX
A3
• Phase 3 current MAX
MAX
AN
• Neutral current MAX*
MAX
A∑
• System current MAX
MAX
+P1
• Phase 1 imported active power MAX
MAX
-P1
• Phase 1 exported active power MAX
MAX
+P2
• Phase 2 imported active power MAX
MAX
-P2
• Phase 2 exported active power MAX
MAX
+P3
• Phase 3 imported active power MAX
MAX
-P3
• Phase 3 exported active power MAX
MAX
+P∑
• System imported active power MAX
MAX
-P∑
• System exported active power MAX
MAX
+S1
• Phase 1 imported apparent power MAX
MAX
-S1
• Phase 1 exported apparent power MAX
MAX
+S2
• Phase 2 imported apparent power MAX
MAX
-S2
• Phase 2 exported apparent power MAX
MAX
+S3
• Phase 3 imported apparent power MAX
MAX
-S3
• Phase 3 exported apparent power MAX
MAX
+S∑
• System imported apparent power MAX
MAX
-S∑
• System exported apparent power MAX
MAX
+Q1
• Phase 1 imported reactive power MAX
MAX
-Q1
• Phase 1 exported reactive power MAX
MAX
+Q2
• Phase 2 imported reactive power MAX
MAX
-Q2
• Phase 2 exported reactive power MAX
MAX
+Q3
• Phase 3 imported reactive power MAX
MAX
-Q3
• Phase 3 exported reactive power MAX
MAX
+Q∑
• System imported reactive power MAX
MAX
-Q∑
• System exported reactive power MAX
MAX
+PF1
• Phase 1 inductive power factor MAX
MAX
-PF1
• Phase 1 capacitive power factor MAX
MAX
+PF2
• Phase 2 inductive power factor MAX
MAX
-PF2
• Phase 2 capacitive power factor MAX
MAX
+PF3
• Phase 3 inductive power factor MAX
MAX
-PF3
• Phase 3 capacitive power factor MAX
MAX
+PF∑
• System inductive power factor MAX
MAX
-PF∑
• System capacitive power factor MAX
MAX
* The neutral current and the derivative parameters (AN, THDAN, HaAN) are not available if the set CT ratio or FSA value is different for each phase.
62
INTE G Er
F. code
Sign
register
(Hex)
words
(Hex)
03 / 04
0200
03 / 04
0202
03 / 04
0204
03 / 04
0206
03 / 04
0208
03 / 04
020A
03 / 04
020C
03 / 04
020E
03 / 04
0210
03 / 04
0212
03 / 04
0214
03 / 04
0216
03 / 04
0218
03 / 04
021C
03 / 04
0220
03 / 04
0224
03 / 04
0228
03 / 04
022C
03 / 04
0230
03 / 04
0234
03 / 04
0238
03 / 04
023C
03 / 04
0240
03 / 04
0244
03 / 04
0248
03 / 04
024C
03 / 04
0250
03 / 04
0254
03 / 04
0258
03 / 04
025C
03 / 04
0260
03 / 04
0264
03 / 04
0268
03 / 04
026C
03 / 04
0270
03 / 04
0274
03 / 04
0278
03 / 04
027A
03 / 04
027C
03 / 04
027E
03 / 04
0280
03 / 04
0282
03 / 04
0284
03 / 04
0286
IE E E
register
M.U.
words
(Hex)
2
mV
1200
2
2
mV
1202
2
2
mV
1204
2
2
mV
1206
2
2
mV
1208
2
2
mV
120A
2
2
mV
120C
2
2
mA
120E
2
2
mA
1210
2
2
mA
1212
2
2
mA
1214
2
2
mA
1216
2
4
mW
1218
2
4
mW
121A
2
4
mW
121C
2
4
mW
121E
2
4
mW
1220
2
4
mW
1222
2
4
mW
1224
2
4
mW
1226
2
4
mVA
1228
2
4
mVA
122A
2
4
mVA
122C
2
4
mVA
122E
2
4
mVA
1230
2
4
mVA
1232
2
4
mVA
1234
2
4
mVA
1236
2
4
mvar
1238
2
4
mvar
123A
2
4
mvar
123C
2
4
mvar
123E
2
4
mvar
1240
2
4
mvar
1242
2
4
mvar
1244
2
4
mvar
1246
2
2
0,001
1248
2
2
0,001
124A
2
2
0,001
124C
2
2
0,001
124E
2
2
0,001
1250
2
2
0,001
1252
2
2
0,001
1254
2
2
0,001
1256
2
MODBUS rTU/ASCII, TCP
M.U.
V
V
V
V
V
V
V
A
A
A
A
A
W
W
W
W
W
W
W
W
VA
VA
VA
VA
VA
VA
VA
VA
var
var
var
var
var
var
var
var
-
-
-
-
-
-
-
-