Herunterladen Inhalt Inhalt Diese Seite drucken

BERG UBN 309 Bedienungsanleitung Seite 69

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

re g i ste r de s crip tion
INSTrUMENT INFOrMATION
Serial number
Firmware release
Hardware version
Model
COM features
Reserved
Digital output number
Digital input number
Reserved
Calibration date
Reserved
Error code
MODBUS rTU/ASCII, TCP
INTE G E r
F. code
register
(Hex)
words
(Hex)
03 / 04
2000
6
03 / 04
2006
2
03 / 04
2008
2
03 / 04
200A
2
03 / 04
200C
2
03 / 04
200E
2
03 / 04
2010
2
03 / 04
2012
2
03 / 04
2014
2
03 / 04
2016
2
03 / 04
2018
4
03 / 04
201C
2
Da ta mea nin g
10 ASCII characters, $00...$FF
Convert the read hexadecimal value in
decimal format.
e.g. $64=100=rel. 1.00
Convert the read hexadecimal value in
decimal format.
e.g. $64=100=rev. 1.00
$0A=1/5A CT
$0C=Rogowski inputs
$02=RS485 port (MODBUS RTU/ASCII)
$03=ETHERNET port (HTTP, MODBUS TCP)
$02=2
$01=1
UnixTime format. Convert the read
hexadecimal value in decimal format.
e.g. $0837$B4C0=1378684800
>09/09/13, 00:00:00
Bit encoding (0=disabled, 1=active):
b1(LSb)=wrong phase sequence (132)
b2=overflow parameter/s
b3=date&time lost, recordings
automatically disabled
b4=unable to generate pulses on
digital output enabled in pulse mode
e.g. $0000$0006=0110
>overflow parameter/s and
date&time lost occurred