6.2.7
Manual address allocation via reader keypad, "stand alone" operating
mode
With this form of address allocation a
an address collision may occur later during operation. (Double or multiple addressing).
Allocate address
Reconnect the reader
Enter the address via the keypad (1 or 2 digit) and confirm with the OK button (
operating voltage is interrupted, the address is saved in the reader.
Overwrite address
The address can be overwritten as long as the reader has not been linked by the AC central control
unit and the operating voltage is not interrupted.
Clear address
An address is
cleared
pressed whilst the operating voltage is re-applied.
An address can also be deleted in the programming mode „Stand alone" (see 7.2)
Note
:
If the reader is connected at a later stage to the AC central control unit, the entered
address is transmitted together with the unique number of the reader to the AC central
control unit and stored.
6.3

Clear addresses

-
Via programming in NetEdit
-
or in "stand alone" operating mode (see 6.2.7)
-
or in "stand alone" programming mode (see Chapter 7)
6.4

Adjustment mode - range

In the adjustment mode you can alter the transmission range between the reader and the
transponder. Note that the distance does not fall short of or exceed a minimum/maximum range
depending on the mounting surface.
Basically, the range should be adapted to a metal mounting surface. It is assumed that the maximum
possible transmission range is lower on a metallic surface than on a non-metallic surface.
Adjustment process:
Hold a transponder at the required distance to the reader. The reading unit in the reader alters the
power of the electromagnetic field in stages (16 stages from max. to min.) and checks at which power
stage the transponder can still be read error-free. This cycle is repeated twice. The value determined
in this manner is stored non-volatile in the reader (until the next adjustment) and can be used for
future applications as a limit value for the maximum possible range.
This range adjustment is not highly precise. This mode serves primarily to ensure that the
reader operates correctly on a metallic mounting surface.
Mounting and Operating Instructions - proX2-reader "Accentic" with keypad
only
to the operating voltage (12 V DC).
when the
keys "1", "7"
(only 026421.10)
plausibility check
and
"X"
are pressed simultaneously and keep
(only 026421.10)
is not possible. This means that
3
). When the