Configuration Possibilities; Dip Switch Setting; Terminal Allocation; Mounting - Honeywell Insertic-Serie Montage- Und Bedienungsanleitung

Berührungsloser leser zur integration in standard-schalterdosen
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

8
4.

Configuration possibilities

Clock/Data
Host-
System
max. cable length 10 m
RS-485-Bus (2-wire)
Host-
System
max. cable length 1200 m
5.

DIP switch setting

The factory settings of the DIP switches are preset according to the
individual reader type. Only the DIP swiches that are required for a
corresponding function may be changed!
5.1
DIP switch setting RS-485 readers
DIP
1
2
TOP
4
8
16
DIP switch
Function
S1 - S5
RS-485 Address
S6 OFF internal used, don't change!
OFF RS-485 without EOL resistor
S7
ON
RS-485 with EOL resistor
OFF power supply front module active
S8
ON
power supply front module disabled
5.2
DIP switch setting
DIP
Function
switch
S4
internal used
S5
OFF
internal used, don't change!
S6
internal used
S7
OFF
power supply front module active
S8
ON
power supply front module disabled
Only proX readers
proX card type
S1
S2
Function
OFF
OFF
EM4x02/V4x50 (factory
ON
OFF
Hitag1/Hitag S
OFF
ON
Hitag2
ON
ON
not allowed
Only LEGIC readers
DIP
Function
switch
S1
ON
Buzzer booking message
S2
ON
Buzzer signal like green LED (input 1)
S3
ON
Buzzer signal like red LED (input 2)
Power supply
LED control
Clock/Data
Power supply
RS-485 Bus
16x on ACS-8,
4x on IK3 EU,
2x on DCM
DIP switch
Address
1
2
3
4
5
1
1
0
0
0
0
2
0
1
0
0
0
3
1
1
0
0
0
4
0
0
1
0
0
5
1
0
1
0
0
6
0
1
1
0
0
7
1
1
1
0
0
8
0
0
0
1
0
1
0
0
1
0
.
.
.
1
1
1
1
1
0
0
0
0
0
Details to the EOL resistor
see Installation Instuction of
the Controller.
Clock/Data readers
1
2
3
4
5
6
7
8
Clock/Data / Wiegand
S3
Function
OFF
Clock/Data
ON
Wiegand
Mounting and Operating Instructions Reader series Insertic
6.

Terminal allocation

ST1
1
2
3
4
5
6
7
Terminal ST3 must remain free!
Terminal specification:
Lift system / connection diameter 0.3 - 1.5 mm / stripped length of wire 6 mm
The wiring of the back module must be done in voltageless
condition, which means the operating voltage must may be
switched on after finishing the complete installation only.
7.

Mounting

Guidelines:
Between contactless readers must be a
Do
not
install the reader
reading distance.
Avoid
direct sun rays
The reader should not be exposed to
1
Perform installation:
2
Prepare the connection cables for the interface and the power supply and prepare
3
4
them for connecting.
5
6
To install the reader, the front module must be
7
8
separated from the back module at first.
9
1. Remove locking screw
2. Insert any cylindrical object with max.
31
vertically from below into the gap and press it by
32
stop means upwards in order to runbolt the
front module.
3. Swing open the lower side of the unbolted front
module about 1 cm to the front.
4. Push the front module carefully upwards until it
comes off the upper locking loops.
5. Swing open the front module to the front.
6. Remove the connector of the back module.
Caution!
Do not pull at the red connector
of the front module!
7. Do the wiring of the back module in
voltageless condition
required connection type (see chapter 6.).
8. Screw the back module into a DIN
installation box with a screw distance of
60 mm using the included screws after
wiring.
9. Set the DIP switches 1 to 7 according to the individually required interface (see
chapter 5.).
ST3
Pin no. Clock/Data
1
LED green
2
LED red
3 *
Clock
Wiegand 0
4 *
Data
Wiegand 1
5
internal used internal used
6
0 V
7
+U_b
* Open collector, aktive LOW, max. 10 mA
minimum distance of 1 m
directly on metal
as this would considerably reduce the
.
plastic decomposing solvent vapours
Æ
3 mm
according to the
RS-485
internal used
internal used
B (D*)
A (D)
0 V
+U_b
in all directions.
.
4
O
3
2
2
1
5
6
8