Herunterladen Inhalt Inhalt Diese Seite drucken

General Information; Technical Specifications - BFT LEO B CBB DL2 3 230 L02 Montageanleitung

Vorschau ausblenden Andere Handbücher für LEO B CBB DL2 3 230 L02:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 40

2) GENERAL INFORMATION

TheLEO B CBB DL2 3 230 L02 - LEO B CBB DL2 3 230 SV - LEO B CBB DL2 3 120
F02- LEO B CBB DL2 3 120 F02 PHOT USA16 control panel comes with standard
factory settings. Any change must be made using the programmer with built-in
display or universal handheld programmer. The Control unit completely supports
the EELINK protocol.
Its main features are:
-
Control of 1 single-phase motor
-
Electronic torque control
- Detection of obstacles through safety bar
- Detection of obstacles through encoder (only for LEO B CBB DL2 3 230 L02 - LEO B
CBB DL2 3 120 F02- LEO B CBB DL2 3 120 F02 PHOT USA16)
-
Separate inputs for safety devices
-
Configurable command inputs
-
Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer's job on site easier.
The jumpers concern terminals: 70-71, 70-72, 70-74, 76-77. If the above-
mentioned terminals are being used, remove the relevant jumpers.
protect the dangerous rims according to the provisions of the EN12453
regulation, applying active edges and using the SAFE1 and SAFE2 inputs (for
the active edge models refer to the model table at paragraph 2)
LEO B CBB
LEO B CBB
DL2 3 230
DL2 3 120
L02
F02
Power supply
220-230V~
120V~ ±10%
50Hz/60Hz
Present
Obstacle
Only for sw
detection with
Present
versions
encoder
Output for
terminals 26-27:
AUX3
N.O. contact
configurable
configurable
(24V~/0,5A)
WIRING AND TERMINAL BOARD CONFIGURATION
Terminal
Definition
L
N
GND
10
START + CAP
11
12
START + CAP
13
COND BOOST
AUX 0 - POWERED CONTACT
20
(LEO B CBB DL2 3 230 L02)
(LEO B CBB DL2 3 230 SV)
POWERED CONTACT 120V~
(LEO B CBB DL2 3 120 F02)
(LEO B CBB DL2 3 120 F02 PHOT USA16)
21
AUX 3 - FREE CONTACT (N.O.)
26
LEO B CBB DL2 3 230 L02
(LEO B CBB DL2 3 230 SV)
27
LEO B CBB DL2 3 120 F02
OUTPUT CONFIGURED AS UL
26
LEO B CBB DL2 3 120 F02 PHOT
27
41
+ REF SWE
42
43
JP32
50
51
52
INSTALLATION MANUAL
LEO B CBB
LEO B CBB
DL2 3 120 F02
DL2 3 230
PHOT USA16
SV
120V~ ±10%
220-230V~
50Hz/60Hz
50Hz/60Hz
50Hz/60Hz
MISSING
obstacle
detection,
Present
apply a
Only for sw
safety edge:
versions
ASO SENTIR
7.08
8.08
EDGE 115SK
/ BIRCHER
EP45x99A1
(NOT
SUPPLIED)
AUX3
Output for
audible signal
configurable
Single-phase power supply
LINE
(LEO B CBB DL2 3 230 L02 - LEO B CBB DL2 3 230 SV).
NEUTRAL
Single-phase power supply 120V~ ±10%, 50-60Hz, with earth cable
EARTH
(LEO B CBB DL2 3 120 F02/ LEO B CBB DL2 3 120 F02 PHOT USA16).
Motor connection.
START + CAP Motor Start and capacitor
COM
COM Motor Common
START + CAP Motor Start and capacitor
10-13 Additional "boost" condenser connection (only for LEO B CBB DL2 3 230 SV)
220 230V~
AUX 0 configurable output - Default setting FLASHING LIGHT.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/
GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTE-
NANCE / ANTITAMPERING / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to "AUX output configuration" table.
AUX 3 configurable output - Default setting MONOSTABLE RADIO CHANNEL Output.
MONOSTABLE RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR
LIGHT/ GATE OPEN ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND
MAINTENANCE / GATE STATUS / BISTABLE RADIO CHANNEL / TIMED RADIO CHANNEL.
Refer to "AUX output configuration" table.
ALARM
Activation: 2 consecutive obstacle detections uninterrupted by an end stop
Deactivation: after 300s or after removal of the "STOP" input
USA16
Limit switch common
SWC
Closing limit switch SWC (N.C.). (Do not connect or jump if there is the magnetic limit switch)
SWO
- Opening limit switch SWO (N.C.). (NDo not connect or jump if there is the magnetic limit switch)
Magnetic limit switch connection
24V-
Accessories power supply output.
24V+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
24 Vsafe+
Output active only during operating cycle.
LEO B CBB DL2 3 230 L02-LEO B CBB DL2 3 120 F02-LEO B CBB DL2 3 120 F02 PHOT USA16 - LEO B CBB DL2 3 230 SV
TESTING
The LEO B CBB DL2 3 230 L02 - LEO B CBB DL2 3 230 SV - LEO B CBB DL2 3
120 F02- LEO B CBB DL2 3 120 F02 PHOT USA16 panel controls (checks) the
start relays and safety devices (photocells) before performing each opening
and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.

3) TECHNICAL SPECIFICATIONS

Power supply
Low voltage/mains insulation
Operating temperature range
Thermal overload protection
Dielectric rigidity
Maximum motor power
Accessories power supply
AUX 0
AUX 3/ Output for audible signal
Dimensions
For
Fuses
N° of combinations
Max.n° of transmitters that can be memorized 63
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
4) TUBE ARRANGEMENT Fi g. A
5) TERMINAL BOARD WIRING Fig. B
WARNINGS - When performing wiring and installation, refer to the standards in
force and, whatever the case, apply good practice principles.
AUX3
Wires carrying different voltages must be kept physically separate from each other,
or they must be suitably insulated with at least 1mm of additional insulation.
Wires must be secured with additional fastening near the terminals, using devices
such as cable clamps.
All connecting cables must be kept far enough away from the dissipater.
Description
220-230V
50/60Hz
~
, with earth cable
220-230V~ 50Hz/60Hz
(LEO B CBB DL2 3 230 L02)
(LEO B CBB DL2 3 230 SV)
120V~ ±10% 50Hz/60Hz
(LEO B CBB DL2 3 120 F02/ LEO B CBB DL2
3 120 F02 PHOT USA16)
> 2MOhm 500V
-20 / +55°C
Built into motor
mains/LV 3750V~ for 1 minute
750W
24V~ (demand max. 1A)
24V~safe
220-230V~N.O. (40W max)
(LEO B CBB DL2 3 230 L02)
powered contact
120V~N.O. (40W max)
(LEO B CBB DL2 3 120 F02/ LEO B CBB DL2
3 120 F02 PHOT USA16)
powered contact
NO contact (24V~/max.0,5A)
146x170x60mm
see Fig. B
4 billion
23

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Leo b cbb dl2 3 120 f02Leo b cbb dl2 3 120 f02 phot usa16Leo b cbb dl2 3 230 svLeo d cbb 230vLeo d cbb 120v

Inhaltsverzeichnis