WARNING
The connections inside the DC and AC combiner boxes as well as the
cable glands must be tightened to the right torque. Please refer to the
annex included together this user guide for rated torques of the most
common components. In case a particular component is not found in the
annex, please check with your Weidmüller sales representative.
WARNING
Each terminal inside the combiner box accepts a limited range of usable
wire cross-sections. In order to determine the usable wire cross-sections
please check the annex. In case of doubt, please check with your
Weidmüller sales representative.
CAUTION
If your DC combiner box model is supplied with empty fuse holders, install
the fuse-links while the switch-disconnector is open.
WARNING
Only 1000V or 1500V in accordance with IEC 60269-6 fuse links can be
used in this combiner box. In case of 10x38mm (>= 1000V) or 10x85mm
(<=1500Vdc) fuse-links, only silver-plated fuse-contacts are allowed.
WARNING
The nominal current I
indicated in the specifications sticker placed inside the combiner box.
Order Number: 7791700275 · Ed. 4 · 04-2016
of fuse-links cannot exceed the maximum I
n
n