illustrated in Enclosures 1/A (floor units), 1/B (wall units) and 1/C (concealed units).
1
Enclosure 2 shows the possible configurations of installation.

4.2 TECHNICAL SPECIFICATIONS

2
The specifications directly referred to the unit purchased are indicated on the identification
tag located in the internal side of the machine (see Fig. 1). Technical specifications (standard)
3
concerning installation and use of the fan coil units are listed on Enclosures 2 and 3 of this
manual.
4
5
6
Fig. 1 Label on SAPHIR
7
• Insulation class: I.
• Protection grade: IPX0
• External structure in ABS thermoplastic material
8
• Technical features of the heat exchanger:
-
Max pressure of the hot or cold water for water fan coil:
1600 kPa - with valves: 1000 kPa.
9
-
Min pressure of the hot or cold fluid: It is the one indicated by the designer/installer for
the correct functioning of the system
Min/max water temperature: 5/85 °C
-
10
-
Hardness of water into the heat exchanger: It is the one indicated by the de-
signer/installer for the correct functioning of the system
-
Water flow: see Enclosure 3
+
• Technical features of the fan motor:
-
With each EST fancoil unit there is the possibility to have different air volumes, ac-
cording to the use requirements. The relevant nominal air capacities are indicated
on Enclosure 3 of this manual and they are referred to standard fancoil units, with
clean filters, at the temperature of 20 °C, at sea level and without external static
pressure.
-
EST technology is composed by a brushless motor combined to a dedicated
electronic device (inverter), managed by specific regulators. The controller uses
a modulating signal with 0-10Vdc tension in order to regulate the fan speed.
24