Herunterladen Inhalt Inhalt Diese Seite drucken

Applicable Models; Preparation For Installation - Mitsubishi Electric PAC-BH01EHT-E Installationshandbuch

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 5

3. Applicable models

-
Unit model
PAC-BH01KTT-E
PAC-BH02KTY-E

4. Preparation for installation

• To use this base heater, it is required to have the genuine Relay Box (hereinafter referred to as "Relay Box") manufactured by
Mitsubishi Electric.
• Do not connect the wrong Relay Box. Only the following two models can be connected to this heater.
PAC-BH01KTT-E: U.S./Canada/South America (3-phase 3-wire 208-230 V 60 Hz)
PAC-BH02KTY-E: Europe
• Refer to the Installation Manual of the Relay Box for how to install this base heater and the Relay Box.
• This base heater and the Relay Box must be installed by a dealer or certified technician.
Specifications of the outdoor unit base heater
Output
Power supply voltage
Heater length [mm (inch)]
Heater diameter [mm (inch)]
• The following tools are required to install the base heater. These are field-supplied.
Phillips screwdriver (magnetic tip): Use to remove or install panels.
Phillips screwdriver (Minimum 40 cm, magnetic tip): Use to install or uninstall the mounting brackets, and to screw or unscrew
Ratchet, spanner: Use to fix the mounting brackets to the screw holes on the accumulator. Use when the screws on the
accumulator are hard to remove.
Threaded rod (Minimum 60 cm, M5): Use to install the mounting brackets to the base.
Nippers: Use to cut cable ties.
Tester: Use to check the base heater for proper operation.
Gloves: Use to keep your hands out of direct contact with the heat exchanger fins, hot section, etc.
Helmet or cap: Use to keep your head protected when you bump your head against the outdoor unit fan motor.
Head light: Use when it is too dark to see the bracket mounting area.
• Check that the main power on the outdoor unit is turned off.
• Base heater installation requires many screws to be unscrewed. Do not lose these screws.
• Thoroughly remove the dust from the base of the unit.
Refer to the Installation Manual of the Relay Box for how to install this base heater and the Relay Box.
4
Target sales area
U.S./Canada
South America and other countries
Europe and
other countries
PAC-BH01KTT-E
[W]
162 (208)/198 (230)
[W/m]
104 (208)/127 (230)
[V]
208, 230 V
1554 (62.2)
ø8 (ø0.32)
the screws on the accumulator.
Applicable models
PUHY-P
THMU-A
PUHY-P
TJMU-A
PUHY-HP
THMU-A
PUHY-HP
TJMU-A
PURY-P
THMU-A
PURY-P
TJMU-A
PUHY-P
THM-A
PUHY-P○YHM-A
PUHY-EP○YHM-A
PUHY-P○YJM-A
PUHY-EP○YJM-A
PUHY-HP○YHM-A
PUHY-RP○YJM-A
PURY-P○YHM-A
PURY-EP○YHM-A
PURY-P○YJM-A
PURY-EP○YJM-A
Unit model
PAC-BH02KTY-E
181 (220)/198 (230)/216 (240)
116 (220)/127 (230)/139 (240)
220, 230, 240 V
1554 (62.2)
ø8 (ø0.32)
type
S module
72, 96
72
72, 96
72
72
72
200, 250, 300, 350
200, 250, 300
200
200, 250, 300
200
200, 250
200, 250, 300, 350
200, 250, 300
200
200, 250, 300
200

Werbung

Inhaltsverzeichnis
loading