ABB F-ARI Serie Installation Seite 3

Fehlerstromchutzschalter mit wiedereinschaltung und automatischem tes

Werbung

TECHNICAL DATA /
SPECIFICHE TECNICHE
TÉCNICAS /
SPÉCIFICATIONS TECHNIQUES
Reference Standards
Electrical features
Test features
Mechanical features
Installation
Auxiliary contact
Dimensions
/ LEISTUNGSMERKMALE / ESPECIFICACIONES
Distribution system
Rated voltage U
e
Rated frequency
Rated current I
n
Rated sensitivity I
δn
Type
Poles
Insulation voltage U
i
Minimum test voltage U
Rated non-operating resistance
between live parts and earth Rdo
Rated operating resistance between
live parts and earth Rd
Rated conditional short-circuit Inc
Dielectric test voltage at ind. freq.
for 1 min
Rated impulse withstand voltage
(1,2/50) U
imp
Power loss
Power consumption 4P
Power consumption during operation 41 VA
Test cycle time
Reclosing time
Protection degree
Contact position indicator CPI
Mechanical life
Tightening torque
Ambient temperature
Storage temperature
Type
Operating features
Terminals cross section
Tightening torque
DIN modules
Weight
F-ARI Test
EN61008-1 , VDE V 0664-120
(annex M)
TN, TT, IT
230-400 V a.c. -15% ÷ 10%
50 Hz
25, 40, 63 A
30, 300 mA
A AP-R
2P, 4P
500 V d.c.
195 V a.c.
tmin
8 kΩ (30 mA), 2,5 kΩ(300 mA)
16 kΩ (30 mA), 5 kΩ (300 mA)
10 kA (SCPD – gL fuse 63 A for In 25,
40 A; gL fuse 80 A for In 63 A)
2,5 kV
4 kV
2P: 3.5, 6, 12 W; 4P: 2.2, 5.4, 6.2 W
23,5 (25A) - 6 (40A) - 12 (63A)
< 7 s
< 10 s (6 s check, 3 s reclosing)
IP20 (terminals), IP40 (housing)
yes
4000
2 Nm
-25...+60 °C
-40...+70 °C
NO-NC-NC+pulse (100 ms)
5 ÷ 230 V a.c./d.c. I
2,5 mm
0,4 Nm
5, 7
550, 900 gr
3
ABB
100 mA
max
2