Herunterladen Diese Seite drucken

ABB CP-A CM Betriebs- Und Montageanleitung Seite 12

Vorschau ausblenden Andere Handbücher für CP-A CM:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 4
Technical data - Control module CP-A CM
Data at T
= 25
o
C, if nothing else indicated
A
Type
Technical data
Input
V
Rated input voltage
IN
Input voltage range
Power consumption at 24 V DC
Measuring circuit
Monitoring function
Measuring voltage
Thresholds
Accuracy, tolerance
Hysteresis, related to the threshold value
Max. measuring cycle
Output circuits
Number of contacts
Operating principle
Contact material
Rated operational voltage U e (VDE 0110, IEC/EN 60947-1)
Min. switching voltage
Max. switching voltage
Min. switching current
Max. switching current
Rated operational current I e (IEC/EN 60947-5-1)
AC 12 (resistive)
AC 15 (indicutive) 230 V
DC 12 (resistive)
DC 13 (indicutive)
Mechanical lifetime
Electrical lifetime
Short-circuit proof, max. fuse rating n/c contact
Indication of operational states
green LED "IN 1"
green LED "IN 2"
green LED "OUT"
General data
Duty time
Dimensions W x H x D
Weight
Wire size
fine-strand wire with wire end ferrule
fine-strand wire without wire end ferrule
rigid
stripping length
tightening torque
Degree of protection, enclosure / terminals
Material of enclosure
Protection class
Environmental data
Ambient temperature range
Climatic category (IEC/EN60721)
Damp heat (IEC/EN 60068-2-3)
Mounting, mounting position
Fastening
Vibration (IEC/EN 60068-2-6)
Shock (IEC/EN 60068-2-27)
Isolation data
Rated insulation voltage I i (IEC/EN 60947-1, EN
50178, VDE 0160)
Input / Relay outputs
Rated impulse withstand voltage between all
isolated circuits (IEC 664, VDE 0110
Test voltage between all isolated circuits
Pollution category
Overvoltage category
230 V
24 V
24 V
n/o contact
illuminated, if VIN1 > threshold value of channel 1 = no fault present
illuminated, if VIN2 > threshold value of channel 2 = no fault present
56.5 x 54 x 24 mm / 2.22 x 2.13 x 0.94 in (when mounted)
operation
storage
CP-A CM
24 V DC
13-30 V DC
approx. 1 W
undervoltage monitoring
rated operational voltage
14-28 V
10 % of full-scale value
3-5 % fixed
6 ms
Relays 11-12/14, 21-22/24
2 x 1 c/o contact
closed-circuit principle
AgNi
250 V
24 V
250 V
10 mA
1 A
1 A
1 A
1 A
1 A
30 x 10
6
switching cycles
0.1 x 10
6
switching cycles
2 A gL
2 A gL
illuminated, if VOUT > 3 V = no fault present
100%
0,063 kg / 0.14 lb
2
0.2-2.5 mm
/ 22-14 AWG
0.2-2.5 mm
2
/ 22-14 AWG
2
0.2-4.0 mm
/ 22-12 AWG
7.5 mm / 0.295 inches
0.4 - 0.6 Nm
IP 20 / IP 20
UL94V0
II
-25
o
C ... +70
o
C
o
o
-40
C ... +85
C
3k3
93 % at +40
o
C, no condensation
plugged onto the redundancy unit
snap-on mounting, without any tool
250 V
safe isolation acc. EN 50178
2.5 kV (type test)
1.2 kV AC (routine test)
2
II
12

Werbung

loading