Correction factor for the SET button
during night operation (energy saving)
(with In1 or In2 = 8 or -8)
nSC
During night operation the control set is:
Set Control = Set + nSC
In night mode decimal point flashes.
In1
INP-1 input setting
In2
INP-2 input setting
bEE
Buzzer enable
mOd
Thermostat functioning mode
Password type of protection
P1
( active when PA is not equal 0)
Password
PA
(see P1 for the type of protection)
reL
Release software
Rev. 01-19
8 = Night mode digital input (energy saving,
N.O.)
7 = Stop defrosting remotely (N.O.) (reads
rising edge of impulse)
6 = Start defrosting remotely (N.O.) (reads
rising edge of impulse)
5 = Stand-by remotely (N.O.) (In order to
indicate Stand-By mode, the display shows
'In5' alternating with the current view)
4 = Pump-down pressure switch (N.O.)
3 = Man-in-room alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man-in-room alarm (N.C.)
-4 = Pump-down pressure switch (N.C.)
-5 = Stand-by remotely (N.C.) (In order to
indicate Stand-By mode, the display shows
'In5' alternating with the current view)
-6 = Start defrosting remotely (N.C.) (reads
falling edge of impulse)
-7 = Stop defrosting remotely (N.C.) (reads
falling edge of impulse)
-8 = Night mode digital input (energy saving,
N.C.)
0 = disabled
1 = enabled
0 = Cold function
1 = Hot function
(in this mode defrosting and fan disable Fst are
excluded)
0 = only display set point
1 = display set point, AUX, light access
2 = access in programming not permitted
3 = access in second level programming not
permitted
ECP 202 EXPERT – Parameters Abstract
-20,0 ÷ +20,0 °C
( like In1 )
0...999
0 = not active
indicates software version
0,0 °C
2
1
1
0
3
0
26
(read
only)
Pag. 5