View set point
Change set point
Change menu "User level"
Return
Change menu "Installer level"
Return
VARIABLES
r0
Temperature difference compared to main SETPOINT
Defrost interval (hours)
d0
If d0 = 0 cyclical defrosts Off
End-of-defrost setpoint.
Defrost is not executed if the temperature read by the defrost
d2
sensor is greater than d2. (If the sensor is faulty defrosting is
timed)
d3
Max defrost duration (minutes)
Drip duration (minutes)
At the end of defrost the compressor and fans remain at
d7
standstill for time d7, the defrost LED on the front panel
flashes.
Fan pause after defrost (minutes)
Allows fans to be kept at standstill for a time F5 after dripping.
F5
This time begins at the end of dripping. If no dripping has been
set the fan pause starts directly at the end of defrost.
Minimum temperature alarm
Allows user to define a minimum temperature for the room
A1
being refrigerated. Below value A1 an alarm trips: the alarm
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.
Maximum temperature alarm
Allows user to define a maximum temperature for the room
A2
being refrigerated. Above value A2 an alarm trips: the alarm
LED flashes, displayed temperature flashes and the buzzer
sounds to indicate the problem.
Evaporator sensor temperature display
tEu
(displays nothing if dE =1)
ECP 202 EXPERT – Parameters Abstract
Pag. 2
FUNCTION
LIST OF LEVEL 1 VARIABLES (User level)
MEANING
PRESS
+
/
+
(3 seconds)
+
(3 seconds)
+
+
(3 seconds)
+
(3 seconds)
VALUE
0,2 – 10,0 °C
0 ÷ 24 hours
-35 ÷ 45 °C
1 ÷ 240 min
0 ÷ 10 min
0 ÷ 10 min
-45÷(A2-1) °C
(A1+1)÷99 °C
Evaporator
temperature
Rev. 01-19
DEFAULT
2,0 °C
4 hours
15°C
25 min
0 min
0 min
-45°C
+99°C
read only