If the display capacity of the digital display DVM-LCD is exceeded, the display will show 9.9.9.9.9.. Applicable for all
modes: A new set value will be stored until the mode is changed or until the Module returns autonomously to the function
"Measuring value" approx. 2 minutes after the last key is pressed. In case of error the word Error and arrow up
arrow down
appears.

Technical data

LCD Indicator for SITRANS devices:
Power supply
Reverse polarity protection
Measuring range of input signal
Current self consumption
Voltage drop over the input terminals
Maximal input load capacity
Linearity
Measuring rate
Temperature influence
Functional temperature range
Operating and storage temperature range
Best display read off
Indication
Indication range
Zero and end value adjusting range
Decimal point changeover
Error message
Limit values
Indication of measuring range and limit value overflow
Setting: zero value, end value and unit
Units
- Programmable physical units in mode M13 and M14
- Possibility of free programmable units in mode M15
Programmable damping
Electromagnetic conformity
Installation
Housing and dimensions
Degree of mechanical protection
Connection
Ex protection
Type of protection
Electrical Data and
Ambient Temperature
© Siemens AG, All rights reserved Ⓟ 2012
A5E02635212-04, en, 12/2012
Pressure Transmitter SITRANS P series MKII
Temperature Transmitter SITRANS TF
Field Indicator in field housing SITRANS TF
Temperature Sensor SITRANS TS500
Two-wire cable (Loop current 4 to 20 mA)
Yes
From 3,5 mA to 23 mA
< 3 mA
< 2,1 V (at 23 mA)
≤ 120 mA
< +/- 0,2 %
≥ 2 Hz
< +/- 0,1% / 10K
-25 to 85°C (for use in hazardous area, see Ex certificate)
-40 to 85°C (for use in hazardous area, see Ex certificate)
-10 to 70 °C
Max. 5 digits
- 99999 to + 99999
- 99999 to + 99999
Automatic and manual
Message „Error" at current range overflow (> 21 mA) and
underflow (< 3,6 mA) according to NAMUR NE 43. These limits
can be adjusted between 3,5 and 23 mA.
Free programmable
Message "arrow up" / "arrow down" at over/underflow
With three keys
mA or % or physical units:
°C, °F, °R, K, bar, mbar, mmH
ftHg, psi, Pa, kPa, MPa, g/cm
3
m
/s, l/h, kg/h, t/h, pH, t, mV, V, Ω, A, ppm
Between 0,1 and 100 s (step 0,1 s)
EN 61326-1 (2006)
With two M4 screws and two distance-bolts
fastened to SITRANS field housing
Plastic material
Diameter 65,5 mm; height 12,4 mm (15,4 mm max.)
IP 20 according to EN 60529
Two-wire cable with two-pole connector
(+ and – marked)
II 1G Ex ia IIC T4 Ga
This Module can also be built in devices with the type of Ex
protection II 3G Ex nA IIC T4 Gc under the condition that the
power supply is protected by an 100 mA fuse and on the label
is made unrecognizable the marking „Ex ia IIC T4 Ga" and
„Number of Notified Body"
The correlation between the electrical data and ambient
temperatures are specified in attached Ex certificate
ZELM 11 ATEX 0470 U and also is applied in to
IECEx ZLM 11,0002 U.
O, inH
O, ftH
O, mmHg, inHg,
2
2
2
2
2
, kg/cm
, torr, atm, l/min, m
or
3
/h,