Allows the selection of one of the following functions for the reduced
operation of the circuits where the room sensor is not connected or
taken into account.
- Night Reduced (setting 1) : heating is continued during reduced
periods (the water supply temperature will depend on the choosen
curve). The pump continuously runs.
- Night Stop (setting 0) : the pump and the heating are off, no
heating request will be accepted. The installation's anti-freeze is
ensured however and causes a night reduced operating.
- If a room sensor is connected, the Night Stop is active when the
room temperature is exceeded, the Night Reduced is active when
the room temperature is below its setting value
This parameter is not displayed if the circuit has a room sensor.
P
10: R
ARAMETER
Setting the minimum room temperature which is maintained in the
antifreeze mode for each circuit. This temperature is only controlled
if parameter 8 "ROOM SENSOR INFLUENCE" is anything other than
0. If parameter 8 "ROOM SENSOR INFLUENCE" is equal to 0, this
parameter is not displayed and the set temperature is fixed at 6°C
(non-adjustable).
E
XTERNAL FROST FREE
Below this temperature, the pumps run continuously and the
minimum circuit temperature is respected.
Whan Night Stop operating (setting 0), Night Reduced mode (setting
1) becomes active.
P
12: D
ARAMETER
Enables to make the following selections when a dhw tank is
connected:
- Domestic hot water priority (setting 1):
absolute priority to heating of domestic hot water : the heating
pump is switched off.
- No domestic hot water priority (setting 0):
heating is not cut off during dhw production.
The temperature in the radiators can reach the maximum
programmed value for the boiler while the domestic hot
water tank is being heated.
19/07/07 - 300010273-001-A
9: N
IGHT
OOM ANTIFREEZE TEMPERATURE
P
11:
ARAMETER
(
)
WITH OUTSIDE SENSOR
OMESTIC HOT WATER PRIORITY
P
ARAMETER
The domestic hot water tank is overheated to 70º C every Saturday
from 4 to 5 o'clock. The "anti legionella" function acts to prevent the
development of legionella in the dhw tank, these bacteria are
responsible for legionellosis.
If you want to activate the anti legionella function, you should:
- increase the boiler thermostat setting to 80 °C.
- provide a mixing device preventing water from being distributed at
a temperature greater than 60 in the domestic hot water
distribution network°C.
H
EATING PUMP AND
- Timing the shutdown of the heating pump makes it possible to
prevent overheating in the boiler during the switch from the winter
regime to the summer regime, which could cause the safety
thermostat to trip unnecessarily.
- Timing the hot water filling pump cut off prevents hot water which
is too hot being sent to the heating circuit after the tank is filled
(Not activated on CITY 2.24). It also prevents overheating in the
boiler, which could cause the safety thermostat to trip
unnecessarily.
P
15: C
ARAMETER
Displays the memory number of the remote control.
C
ONTROL NUMBER OF THE MEMORY OF THE CENTRAL PROCESSING
Used to display the memory number of the central boiler unit.
GMR1000: Control number of the memory of the interface board.
P
17: C
ARAMETER
ONTROL MEMORY NUMBER OF THE TRANSMITTER
Used to display the memory number assigned to the transmitter/
receiver box.
RS 100 R
13: A
NTILEGIONELLOSIS
P
14:
ARAMETER
DHW
PUMP TIMEOUT
ONTROL NUMBER OF THE REMOTE CONTROL
.
MEMORY
P
16:
ARAMETER
.
UNIT
RECEIVER BOX
/
11