3 Further information on various parameters
P
ARAMETER
To display the boiler water outlet temperature.
P
ARAMETER
Used to display the boiler water outlet temperature on the valve circuit.
P
3: G
ARAMETER
The factory setting of the heating curve is 1.5
Maximum boiler temperature
Factory setting: 75 °C
Minimum boiler temperature in comfort mode: 30 °C (Factory
setting)
X
Outside temperature
Y
Water flow temperature
P
4: G
ARAMETER
The factory setting of the heating curve is 0.7
Maximum start temperature after valve
Factory setting: 50 °C
Maximum outlet temperature after valve
Factory setting: 20 °C
X
Outside temperature
Y
Valve start temperature
10
1: B
OILER TEMPERATURE
2: F
B
LOW TEMPERATURE
RADIENT OF THE HEATING CIRCUIT
RADIENT OF THE HEATING CIRCUIT
4,0
,0
2,25
2,0
M
The flow temperature for the heating circuit can be limited.
For a standard installation without outside sensor, we
recommend to set the maximum temperature of the
heating circuit to a value less than or equal to 75°C.
A
M
AXIMUM OUTLET TEMPERATURE AFTER VALVE
For circuit B, this setting limits the outlet temperature on the
corresponding circuit.
If using underfloor heating, it is imperative to keep the
factory setting of the maximum outlet temperature after the
mixing valve at 50°C.
The regulations also impose an independent safety device
which must cut off the supply of heat to the underfloor
heating circuit when the maximum temperature of the
liquid reaches 65°C. To meet this requirement, a safety
thermostat must be electrically connected to the TS
contact on the pump connector.
- Enabled (setting 1): automatic setting of the heating curve is
enabled.
- Blocked (setting 0): the heating curve is fixed. It can only be
modified manually.
B
P
ARAMETER
Enables to adjust the influence of the room sensor on the boiler water
temperature.
0: the room sensor is ignored (for example : badly positioned remote
control).
1: Slight influence.
3: Average influence (recommended).
10: operating like room thermostat.
RS 100 R
P
5
ARAMETER
AXIMUM HEATING CIRCUIT TEMPERATURE
P
6
ARAMETER
P
7: S
-
ARAMETER
ELF
ADAPTIVITY
8: I
NFLUENCE OF THE ROOM SENSOR
A
B
19/07/07 - 300010273-001-A