3.5 Installer Parameters Table

3.5.1 Category 1 - Room Unit Settings

Parameter
Parameter
Category 1 Parameters – Room Unit Settings
AM-PM / 24hr
Display
Reset Time/ Temp
Program
Auto Summer/
Winter Time
Change
LCD Backlighting
Upper Temp Limit
Lower Temp Limit
Optimisation
Temperature
Offset
Proportional Band
Width
Reset Parameters
to Factory
Defaults
Note
Remember to always press the green
Set-Up setting. To exit the Installer Mode press the
Factory Default Setting
No.
Display
Description
1:CL
24
24 hr clock display
format
2:rP
1
Time / Temp profile
set to factory default
Changes to 0 when
one of the time/temp
profiles are changed
3:tC
1
Auto Summer/
Winter Time Change
Enabled
5:bL
1
Backlighting Enable
6:uL
35
35°C Upper Temp.
Limit
7:LL
5
5°C Lower Temp.
Limit
8:OP
0
Optimisation
Disabled
12:tO
0
No temperature
offset
13:Pb
1.5
Proportional band of
1.5 degrees
19:FS
1
All settings at factory
defaults
Changes to 0 when
one of the parameter
is changed
button to confirm that you want to store your new Installer
Installation and Operation Manual
Optional Setting
Display Description
12
12 hr – AM/PM clock display
format
0
Time / Temperature are as
programmed
To restore the factory profile set
to 1
0
Auto Summer/Winter Time Change
Disabled
0
Backlighting Disabled
21 to
21°C to 34°C adjustment in 1°C
34
steps
5 to 21
6°C to 21°C adjustment in 1°C
steps
1
Optimisation Enabled
-3 to
-3°C to +3°C adjustment in 0.1°C
+3
steps
1.6 to
1.6°C to 3.0°C adjustment in 0.1°C
3.0
steps
0
Settings are as modified above
To restore the factory profile set
to 1
or
button.