7. Modbus-Register

Coil Modbus register
Coil
register
Register
address
content
0x0001
Override relay value
Discrete Modbus register
Discrete
register
Register
address
content
1x0001
Digital input 1
1x0002
Digital input 2
Input Modbus register
Input
register
Register
address
content
3x0001
MODBUS address
3x0002
Pressure
3x0003
Mean pressure
3x0004
Output voltage (V)
3x0005
Temperature (°C)
3x0006
Digital input 1
3x0007
Digital input 2
3x0008
Alarm relay
3x0009
Setpoint
3x0010
Calibration value
3x0011
Alarm log FIFO #9
3x0012
Alarm log FIFO #8
3x0013
Alarm log FIFO #7
3x0014
Alarm log FIFO #6
3x0015
Alarm log FIFO #5
3x0016
Alarm log FIFO #4
3x0017
Alarm log FIFO #3
3x0018
Alarm log FIFO #2
3x0019
Alarm log FIFO #1
3x0020
Alarm log FIFO #0
Änderungen vorbehalten.
Read/
Value range
Write
0,1 (*10)
R/W
Read/
Value range
Write
0,1
R
0,1
R
Read/
Value range
Write
1 to 247
R
-xPa to +xPa
R
-xPa to +xPa
R
0-100 (*1)
R
-300 to +700 (*1)
R
0,1
R
0,1
R
0,1
R
0Pa to 2000Pa
R
-xPa to +xPa
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
Holding Modbus register
Holding
register
Register
address
content
4x0001
MODBUS address
4x0002
Pressure
4x0003
Mean pressure
4x0004
Output voltage (V)
4x0005
Temperature (°C)
4x0006
Digital input 1
4x0007
Digital input 2
4x0008
Alarm relay
4x0009
Setpoint
4x0010
Manual setpoint
4x0011
Temperature from
MODBUS (°C)
4x0012
Regulator speed
4x0013
Output range low
4x0014
Output range high
4x0015
Operation mode
4x0016
Mean operation
mode
4x0017
Temp. sensor type
4x0018
Temp. compensa-
tion low
4x0019
Temp. compensa-
tion high
4x0020
Temp. compensa-
tion
4x0021
Temp. sensor adjust
(°C)
4x0022
High pressure alarm
trig. (Pa)
4x0023
Low pressure alarm
trig. (Pa)
4x0024
High pressure alarm
enable
4x0025
Low pressure alarm
enable
4x0026
Alarm delay
4x0027
DI1 setpoint
4x0028
DI2 setpoint
4x0029
DI1 function
4x0030
DI2 function
4x0031
Override DAC from
MODBUS
4x0032
Override DAC value
(V)
4x0033
Override relay from
MODBUS
4x0034
Override relay value
4x0035
Calibration value
4x0036
Alarm log FIFO #9
4x0037
Alarm log FIFO #8
4x0038
Alarm log FIFO #7
4x0039
Alarm log FIFO #6
4x0040
Alarm log FIFO #5
DE.TBMZ.190920
Read/
Value range
Write
1 to 247
R
-xPa to +xPa
R
-xPa to +xPa
R
0-100 (*1)
R
-300 to +700 (*1)
R
0,1
R
0,1
R
0,1
R
0Pa to 2000Pa
R
0Pa to 2000Pa
R/W
-300 to +700 (*1)
R/W
0-10
R/W
0-100%
R/W
0-100%
R/W
1-9 (*2)
R/W
1-3 (*3)
R/W
1-5 (*4)
R/W
-20°C to +30°C
R/W
-20°C to +30°C
R/W
0Pa to 500Pa
R/W
-30 to +30 (*1)
R/W
0Pa to 2000Pa
R/W
-50Pa to 2000Pa
R/W
1,2 (*9)
R/W
1,2 (*9)
R/W
0-10min
R/W
0Pa to 2000Pa or
R/W
0-100 (*1,6)
0Pa to 2000Pa or
R/W
0-100 (*1,6)
1,2,3,5,7 (*5)
R/W
1,2,3,5,7 (*5)
R/W
0,1
R/W
0-100 (*1,7)
R/W
0,1
R/W
0,1 (*10)
R/W
-xPa to xPA
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R
0-7 (*8)
R