Herunterladen Inhalt Inhalt Diese Seite drucken

Gps Model; Gps : Setup - Valpes VR-Serie Installations- Und Bedienungsanleitung

Elektrisch
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

UK
GPS: description
GPS models include a Failsafe unit and a Positioning unit (GS2 connected to GP5).
There are two available settings: 0-10V and 4-20mA.

Normaly closed: 0-10V : 0° 0V / 90° 10V and 4-20mA : 0° 4mA / 90° 20mA

Normaly open: 0-10V : 90° 0V / 0° 10V et 4-20mA : 90° 4mA / 0° 20mA
GPS: warnings

Do not connect the input signal directly to terminals 15 & 16 of the Positioning unit (SNAA480000) of the GPS
model. The input signal positive (+) must first be connected in series with terminals 67 & 68 of the Failsafe unit
(SNAA550000) to ensure the actuator closes in case of power failure. This contact must be wired with positive DC
only.

Be sure you connect the terminal 15 (-) before the terminal 16 (+)

Following a power failure, the Failsafe unit will reset after 3 minutes.

GPS : setup

Terminals 17 & 18 of the Failsafe unit (SNAA550000) must be disconnected prior to any programming of the Positio-
ning unit. Isolate these cables to prevent short-circuits
To proceed at the setup of the card, refer to page 41
the
44
ENGLISH
DSBA3400 • Rév. 24/01/2019

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis