Herunterladen Inhalt Inhalt Diese Seite drucken

Power Supply - Valpes VR-Serie Installations- Und Bedienungsanleitung

Elektrisch
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

ENGLISH
UK
POSI: electric diagram
Rep.
Designation
FC0
Open limit switch
FCF
Close limit switch
D1/D2 Failure report Terminal strip (24V DC / 3A max)

For GPS models, refer to the section p.44 et 45.

The terminal temperature can reach 90°C.

The used wires must be rigid (feedback voltages: 4 to 250V AC/DC).

For a use with a long power supply wiring, the induction current generated by the wires mustn't be higher than
1mA.

The control voltage must be S.E.L.V. (Safety Extra Low Voltage).

No common earth/ground connexion between the control (input and output signal) and the alimentation. (Type 0-20
or 4-20mA : 5V DC max.)

POWER SUPPLY

N
TP/PE
100V-240V 50/60Hz (100V-350V DC)
15V-30V 50/60Hz (12V-48V DC)
D1
D2
+
16
-
15
-
14
+
13

i
The card resolution is 1°

10 kOhm input impedance if control with voltage (0-10V) and 100 Ohm input impedance if control with current (0-20mA ou
4-20mA)
40
Rep.
Designation
FC1
Auxiliary limit switch 1
FC2
Auxiliary limit switch 2
Ph
-
+
1
2
3
17
18
17
18
A
A
C
~
+
~
B
Motor
=
FEEDBACK
4
5
6
7
SNAA690000
DSBA3400 • Rév. 24/01/2019
8
9

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis