Herunterladen Inhalt Inhalt Diese Seite drucken

Connections Left And Right Models; Installation Recommendation Regarding Condensation; Condensation Inside Of The Unit; Condensation Outside Of The Unit - SystemAir SAVE VTR 250/B Installationsanleitung

Vorschau ausblenden Andere Handbücher für SAVE VTR 250/B:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

10
| Technical Data
4.3

Connections Left and Right models

Position
R
L
Symbol
Description
Supply air
Exhaust air
4.4

Installation recommendation regarding condensation

4.4.1

Condensation inside of the unit

When the unit is installed in a cold attic (close to outdoor temperature) the unit should run continuously. If the unit is in-
tended to be stopped by the user manually or due to calendar function we recommend to install air tight dampers at ex-
tract and supply air ducts. The dampers will ensure that no air circulates from the warm parts of the building through
the unit to outside (chimney effect). If no dampers are installed there is risk of condensation inside the unit and the out-
door ducts during these stop periods. It also might be that cold air from outside could pass the unit and enter into the
building. That could cause condensation outside the supply and extract air ducts and even at the valves in the rooms.
When the unit is not running due to late commissioning in winter time, the supply and extract air ducts should be dis-
connected and closed due to above mentioned effects until commissioning and regular operation.
4.4.2

Condensation outside of the unit

When the unit is installed in warm humid areas (like laundry) together with low outdoor temperature there is a certain
point where moisture can condense outside of the casing. The condensation relation to indoor relative humidity, room
and outdoor temperature is shown diagram below. The condensation outside of the unit do not occur in zones bellow
each curve.
Important
Recommendation: If condensation occurs, increase ventilation in area close to the unit.
Description
Right hand model (Supply air connection is situated on the right hand side of the unit
viewed from the front)
Left hand model (Supply air connection panel is situated on the left hand side of the unit
viewed from the front)
Symbol
Description
Outdoor air
Extract air
Symbol
Description
Cooker hood air
213006 | v01_1.8.0
GB

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Save vtc 500