ELECTRICAL WORK

1. Using the specified wires, ensure to connect
the wires, and fix wires securely so that the
external tension to the wires do not affect the
connecting part of the terminals.
Incomplete connection or fixation may cause a
fire, etc.
2. Be sure to connect earth wire. (grounding
work)
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for
telephone wires.
3. Appliance shall be installed in accordance
with national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
• Wrong wiring may cause a burn-out to some
electrical parts.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core
and inner insulator of power and inter-connecting
wires when peeling them.
• Use the power and Inter-connecting wires with
specified thickness, specified type and protective
devices required.
• Remove the panel, and you can see electric
parts on the front side.
• A metal pipe can be installed through the hole
for wiring. If the hole size does not fit the wiring
pipe to be used, drill the hole again to an
appropriate size.
• Be sure to clamp the power wires and indoor/
outdoor connecting wires with banding band
along the connecting pipe so that the wires do
not touch the compressor or discharge pipe.
(The compressor and the discharge pipe
become hot.)
WARNING
CAUTION
– 16 –
Outdoor Unit Installation Manual
Furthermore, be sure to secure these wires with
the pipe valve fixing plate and cord clamps stored
in the electric parts box.
Electric parts box
Pipe valve
fixing plate
Cord
clamp
Pipe hole
Wiring between Indoor
Unit and Outdoor Unit
The dashed lines show on-site wiring.
(Main circuit)
Input
L
power
N
220-240 V~,
50 Hz
Outdoor unit
Earth
Leakage
breaker
• Connect the indoor/outdoor connecting wires to
the identical terminal numbers on the terminal
block of each unit.
Incorrect connection may cause a failure.
For the air conditioner, connect a power wire as
mentioned below.
Model RAV-
Power supply
Maximum running
current
Installation fuse rating
H07 RN-F or 60245 IEC 66
Power wire
Indoor/outdoor
H07 RN-F or 60245 IEC 66
connecting wires
H07 RN-F or 60245 IEC 66
Earth wire
Panel
(Indoor/outdoor
connecting wires)
1
1
2
2
Remote
3
3
controller
Indoor unit
Earth
SM160
220-240 V~, 50 Hz
32 A
40 A
(all types can be used)
2
(6.0 mm
or more)
2
(1.5 mm
or more)
2
(1.5 mm
or more)
16-EN