 Mounting plate
 Wireless remote controller
 Drain socket

CHOOSING AN INSTALLATION SITE

• Before choosing the installation site, obtain user approval.

Indoor Unit

The indoor unit should be sited in a place where:
• The restrictions on installation specified in the
indoor unit installation drawing are met.
• Both air intake and exhaust have clear paths met.
• The unit is not in the path of direct sunlight.
• The unit is away from the sources of heat or steam.
• There is no source of machine oil vapour (this may
shorten indoor unit life).
• Cool air is circulated through out the room.
• The unit is away from electronic ignition type
flourescent lamps (inverter or rapid start type). As
these may shorten the remote controller range.
• The unit is at least 1 metre away from any
television or radioset (unit may cause interference
with the picture or sound).
• Install at the recommended height (more than
2.7m).
• Do not install the units at or near doorway.
• Do not operate any heating apparatus too close
to the air conditioner unit or use in room where
mineral oil, oil vapour or oil steam exist, this may
cause plastic part to melt or deform as a result of
excessive heat or chemical reaction.
• When the unit is used in kitchen, keep flour away
from going into suction of the unit.

ACCESSORIES

 Remote controller holder
1
1
 Fixing screws for remote
controller holder M3 × 16L
1
 Drain plug
*Only for heat pump models.
1-9
1
 AAA dry-cell batteries
2
 Titanium apatite
photocatalytic air-purifying
filter
 Installation manual
1
 Operation manual
• This unit is not suitable for factory used where
cutting oil, mist or iron powder exist or voltage
fluctuates greatly.
• Do not install the units at area like hot spring or oil
refinery plant where sulphide gas exists.
• Ensure the color of wires of the outdoor unit and
the terminal markings are same to the indoors
respectively.
• IMPORTANT : DO NOT INSTALL OR USE THE
AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
Do not use joined and twisted wires for incoming
power supply.
The equipment is not intended for use in a
potentially explosive atmosphere.

Wireless Remote Controller

• Do not expose the remote controller to direct
sunlight (this will hinder receiving signals from the
indoor unit).
• Turn on all the fluorescent lamps in the room,
if any, and find the site where remote controller
signals are properly received by the indoor unit
(within 7 metres).