Herunterladen Inhalt Inhalt Diese Seite drucken

Memorization Procedure - tau K120M Installationsanleitung

Vorschau ausblenden Andere Handbücher für K120M:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 22
2
nd
16 - 17
CHANNEL
18 - 19
ANTENNA
M5
ENCODER
20 - 21 - 22
ENCODER
24V DC
23 - 24
MOTOR
M6
BATTERY

MEMORIZATION PROCEDURE

WARNING: After powering the control panel, wait 2 seconds before you start performing the
adjustment operations.
Note: The gate must be equipped with the opening and closing safety stops.
When you have completed the installation procedures :
1_ bring the gate to approx. 1 m from the closing travel limit;
2_ set dip-switch no. 10 to ON;
3_ operate the automation using one of the following inputs: A/C, radio control or card button (O/C);
4_ the gate must start to close.
Note: if it opens, stop the programming procedure by resetting the electric panel (disconnect
the power supply to the panel for at least 5 sec. and set dip-switch no. 10 to OFF); with
the control panel disconnected, exchange the motor supply wires. Restart the proce-
dure from point 1.
5_ when the gate has closed, after approximately 2 seconds a complete opening manoeuvre is ex-
ecuted automatically;
6_ when the gate has opened, wait for the DL3 led to be fixedly on, then set dip-switch no.10 to OFF;
7_ the automation is now ready for operation.
Make the logic adjustments.
Note: When any adjusting devices (trimmers or dip-switches) on the control panel are oper-
ated, a complete manoeuvre must be carried out in order for the new settings to take
effect.
LOGIC ADJUSTMENTS
TRIMMER
RALL.
Deceleration adjustment: from 0 to 150 cm before the limit switch;
Note: the automation must perform a complete opening and closing ma-
noeuvre before setting the deceleration.
FR.
Obstacle detection sensitivity adjustment. The trimmer is set to provide suffi-
cient thrust to work the gate without exceeding the limits established by current
standards (EN 12453). Turning the trimmer clockwise (+) increases the mo-
tor torque, turning it anticlockwise (-) reduces it.
T.C.A.
Automatic Closing time adjustment: from about 3 to 255 seconds (see dip-
switch no. 1);
2
RADIO CHANNEL output (its operation depends on dip-
nd
switches nos. 7 - 8) to be used for opening/closing another gate,
for controlling garden lights or for the "ZONE LIGHTING" func-
RADIO
tion.
Warning: to connect other devices to the 2nd Radio Chan-
nel (area lighting, pumps, etc.), use an additional auxiliary
relay.
433,92 MHz built-in RX ANTENNA input.
18= EARTH, 19= SIGNAL.
quick coupling for ENCODER connection.
White= 0 V DC (GND), brown= 5 V DC (+5V),
green= ENCODER SIGNAL (ENC).
encoder supply and input
20 white= 0 V DC (GND), 21 brown= 5 V DC (+5V),
22 green= ENCODER SIGNAL (ENC).
MOTOR supply output 24 V DC, max. 50 W.
23= NEGATIVE, 24= POSITIVE.
quick coupling for BATTERIES 19,2 V DC - 1,2 Ah connection.
K120M
RALL
-
+
FR
-
+
TCA
-
+
17

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis