3. Specifications
Adjustability of zero point and span
Adjustment is made using potentiometers inside the instrument.
Not possible for IP68 cable outlet.
Zero point: ± 5 %
Span:
± 5 %
3.6 Time response
Settling time: ≤ 2 ms

3.7 Operating conditions

Ingress protection (per IEC 60529)
The ingress protection depends on the type of electrical connection.

Electrical connection

Angular connector DIN 175301-803 A
Circular connector M12 x 1 (4-pin)
Cable outlet IP67
Cable outlet IP68
1) Adjustability of zero point and span not possible.
The stated ingress protection only applies when plugged in using mating connectors that have the appropriate ingress
protection.
Vibration resistance
Process connections without cooling element: 20 g (IEC 60068-2-6, under resonance)
Process connections with cooling element: 10 g (IEC 60068-2-6, under resonance)
Shock resistance
Process connections without cooling element: 1,000 g (IEC 60068-2-27, mechanical)
Process connections with cooling element: 400 g (IEC 60068-2-27, mechanical)
WIKA operating instructions pressure transmitter, model S-11
Ingress protection
IP65
IP67
IP67
IP68
1)