FC410DDM – UNIVERSAL FIRE AND GAS DETECTOR MODULE
DESCRIPTION
The FC410DDM provides the ability to connect and interface 2 zones of 20 V
DC 2-wire conventional fire detectors, or two 4-20 mA signalling sensors, to
the FireClass fire alarm controller.
The FC410DDM monitors the status of the detectors and the wiring to the
detectors and signals detector and wiring status back to the controller.
The conventional detector circuits can be configured in one way:
Ø To monitor 1 or 2 Class B spur circuits
The 4-20 mA signalling sensors may be one of two types:
Ø Current sinking
Ø Current sourcing

TECHNICAL SPECIFICATION

Type Identification Value:
System Compatibility:
Environment:
Operating Temperature:
Storage Temperature:
Operating Humidity:
Dimensions (WxHxD)
PCB: 84x60x25 mm (includes LED on rear)
Cable Termination:
Detector Circuits (x 2):
– Detector Circuit Supply Voltage: 22 V nominal (22.5 max.)
– Detector Circuit Supply Voltage Low: 21 V, 14.5 V for Series 600 detectors
in Loop Power mode
Detector Circuit Current Limit:
– 25 mA (22 min., 27 max.)
Detector Current per Circuit:
Detector Circuit Resistance:
EOLs (End of Line Devices)
Conventional Circuit:
4-20 mA signalling sensors:
– No EOL for current sinking sensor
– 220 Ohms, 1 % for current sourcing sensor
4-20 mA Current Sensing
Sense
Resistor:
– Internal to FC410DDM for current sinking sensors
– Fit to terminals for current sourcing sensors
Insertion Voltage:
– 5 V max. (Compliance Voltage)
– 4.4 V/20 mA
Relative to 0 V when FC410DDM sinking (i.e., for current sourcing sensor). Rel-
ative to FC410DDM 22 V supply when sourcing (i.e., for current sinking sensor).
FC Loop Voltage
Max. Loop Voltage:
Min. Loop Voltage:
– 28 V DC (all loop power modes except for only Series 600 detectors)
– 21 V DC (external power or on Series 600 detectors on loop power)
External 24 V PSU Voltage:
Battery Requirements – External Power Mode
From Addressable Loop
– Standby
Current:
– Alarm
Current:
From 24 V PSU
Fixing instructions Doc. version 2.0 09 February 12
149
Use only with FireClass Fire Alarm
Controllers
Indoor Application only
-25° to +70°C
-40° to +80°C
Up to 95% RH non-condensing
2.5 mA max.
50 Ohms max.
4.7 kOhms, 1 % standard
Value 220 Ohms, 1 % 0.25 W
40 V DC
21.9 V to 29 V
2.2 mA per FC410DDM (1.1 mA per
cct for Class B)
7.7 mA per FC410DDM (Alarm LED on)
ENGLISH
– Class B Standby Current, 4,7
kOhms EOL:
– Class B Alarm Current :
Battery Requirements – Loop Power Mode
From Addressable Loop:
– Class B Standby
Current:
– Class B Alarm Current:
– Class B S/C Fault Current:
Electromagnetic Compatibility
The FC410DDM complies with the following:
– Product family standard EN 50130-4 for immunity
– EN 61000-6-3 for emissions
ADDRESS SETTING
The FC410DDM has a default factory set address of 255, that must be set to
the loop address for the device. The FC410DDM may be programmed prior
to installation by using the FC490ST Service Tool and the internal program-
ming port (see Fig. 1).
+
This device use one address only on the loop.
+
Note: Once the address has been programmed, take note of the device
location and address number, to include on site drawings.
IDENTIFICATION OF PARTS
See Figs 1, 2, 3, 4, 5, 6 and 7.
1
Programming port for FC490ST
2
Label
3
Terminal identification label
4
EOL
5
From 24 V PSU
From previous device -
6
FC Loop
7
To next FC410DDM
CABLING
Cables are to be selected in accordance with the system design document
and the requirements of the applicable standards.
The maximum section of the cable that can be connected at any one termi-
nal is 2.5mm
2
.The section is calculated based on the characteristics of the
cable and the load.
1
Fig. 1: FC410DDM – Universal fire and gas detector module
FC410DDM – Universal fire and gas detector module
10 mA per FC410DDM/5 mA per cct
(excludes detector load)
52 mA per FC410DDM/26 mA per cct
4.6 mA No load (both ccts open)
20 mA per FC410DDM + det load x
1.82/10 mA per cct + det load x 1.82
100 mA per FC410DDM (2 ccts in
alarm, Alarm LED on)
95 mA per FC410DDM/48 mA per cct
To next device -
8
FC Loop
9
From FC410DDM
10 From PSU
11 Supply
12 Signal
4-20 mA Current Sinking
13
Sensor