Herunterladen Inhalt Inhalt Diese Seite drucken

General; Electrical Specification; Operating Limits; Air Temperature Limits - SystemAir K OG 30 LN 2T Installations- Und Wartungshandbuch

Kaltwasser oder geheizteswasser -kassette
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 44
CHILLED WATER CASSETTE
3
3.1

ELECTRICAL SPECIFICATION

Models
Nominal current
Maximal current
Fuse rating gG
Fuse rating ASE / VDE
Power supply
Cable section mini*
Electric heating capacity
Models
Nominal current
Maximal current
Fuse rating gG
Fuse rating ASE / VDE
Power supply
Cable section mini*
Electric heating capacity
* Minimum cable diameter to be determined in accordance with installation conditions and local
standards.
** aM or C curve trip switch
1 thermostat for each cassette or installation with the 7ACEL1207 kit for a MAXIMUM of
4 Cassettes.
3.2

OPERATING LIMITS

AIR TEMPERATURE LIMITS

Minimum ambient temperature (wb)
Minimum ambient temperature (db)
Maximum ambient temperature (wb)
Maximum ambient temperature (db)

WATER TEMPERATURE LIMITS

Minimum water inlet temperature
Maximum water inlet temperature
Please consult us for operating conditions exceeding these temperatures.
G
eneral
with heating
A
4.76
A
5.61
A
8
A
8
3N ~ 400V - 50Hz
mm²
5G1.5
W
2 800
with heating
A
4.76
A
5.61
A
8
A
8
3N ~ 400V - 50Hz
mm²
5G1.5
W
2 800
Cooling
13 °C
17 °C
22 °C
32 °C
db: dry bulb wb: wet bulb
Cooling
5 °C
18 °C
6
30 2T
without heating
12.87
0.7
15.43
0.99
16
2 **
16
2
230V 50Hz
230V 50Hz
3G4
3G1.5
2 800
/
45 2T
without heating
12.87
0.7
15.43
0.99
16
2 **
16
2
230V 50Hz
230V 50Hz
3G4
3G1.5
2 800
/
Standard unit
Heating
/
/
22 °C
32 °C
Standard unit
Heating
2T / 4T
2T with heating
/
/
70 °C
35 °C
45 4T
/
0.70
0.99
2 **
2
230V 50Hz
3G1.5
/

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

K og 45 ln 4t

Inhaltsverzeichnis