Installation

Level
Measurement reference height
Figure 4-1
Mounting the pressure transmitter (example with protective cover made of PPE)
1. Install the pressure transmitter suspended downward on the cable.
2. To prevent measuring errors, fasten the pressure transmitter for moved process media.
3. Fasten the pressure transmitter by means of a guide tube or an additional weight on the transmitter (max. tensile force
on connecting cable 360 N).
4. Fasten the cable above the container with the anchor clamp.
5. Connect the cable itself with the cable box.
6. Mount the cable box at a location appropriate to its degree of protection (IP66) in the vicinity of the measuring point.
7. To ensure proper functioning, make sure that the entry openings on the protective cover of the pressure transmitter do
not get soiled and that the process medium does not freeze on the pressure transmitter.
SITRANS LH300 (7MF1575..) Transmitter for hydrostatic level