Configuring the inverter Modbus interface
Set the following parameters in each inverter:
Parameter
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.10 Refresh settings
Quick installation and start-up guide – SREA-50 9
Setting
1 = Modbus RTU Enables the embedded
0...9
3 = 19.2 kbps
2 = 8 EVEN 1
(default)
1 = Refresh
Description
fieldbus interface.
Defines the node address of
the inverter.
Note: This value must be
unique for each inverter
within a range of 0...9. For
example:
• Inverter 1: 58.03 = 0
• Inverter 2: 58.03 = 1, and
so on.
Two devices with the same
address are not allowed.
Sets the baud rate.
Sets the parity.
Validates the communication
settings.