Herunterladen Inhalt Inhalt Diese Seite drucken

Channel Monitoring - Emerson A6312 Schnellstartanleitung

Drehzahl- / key-monitor
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Product Information / Produktinformation A6312
Rotational Speed Monitor
Signal conditioning for characteristical value
The input signals are scaled before processing. The characteritical value is proportional to the
speed, i.e. the input frequency divided by the number of theeth of the pulse wheel configured
with the configuration software.
Range adjustment
Maximum measuring range
Maximum speed
Maximum number of teeth
Current output − characteristical value
The calculation of the characteristical value and its evaluation depends on the function
determined during configuration.
Current output 1 − I1+ / I1−
Current output 2 − I2+ / I2−
Nominal range
Life zero − mode
Accuracy / resolution
Permissible load

1.6.2 Channel monitoring

Monitoring function
Sensor signals
System voltages
μP function (watchdog)
External disable signal
Status channel monitoring
Channel status = no error (OK)
Channel status = error
determined during configuration
limited by the max. signal frequency of 20 kHz
65535 rpm with 18 teeth,
max. signal frequency = 20 kHz
255
z18 (+) / b18 (−) galvanically isolated
z20 (+) / b20 (−) galvanically isolated
0...20 mA or 4...20 mA, depending on configuration
in the 4...20 mA mode the output con be set to 0 mA
in case of a fault. This function is activated during
configuration.
±1 % of f.s.d. / 16 bit
500 Ω
Constant monitoring
GOOD range (configuration dependent)
Voltage − OK
WD − OK
ES
if (voltage_OK = yes)
AND (WD_OK = yes)
AND (Sensor signal in the GOOD range)
AND (ES = no)
If the previous condition is not satisfied