Product Information / Produktinformation A6312
Rotational Speed Monitor
Visualization
Green LED on the front panel
Channel status = no error (OK)
Channel status = error
Gap error
configuration error / watchdog
Channel Clear outputs
Opto−decoupled collector/emitter segments
Channel Clear channel 1, C1C / C1E z26 (collector) / z28 (emitter)
Channel Clear channel 2, C2C / C2E z30 (collector) / z32 (emitter)
Ext. disabled or status = error
Not ext. disabled and status = OK
Binary inputs
Signal level
External locking
z22 − for locking the function / alarm outputs e.g. for service works etc.
Disable / locking
Enable / unlocking
Reset Latch
d20 − for resetting the latch function of the function output
Reset
no Reset
Test channel 1 / channel 2
z12 / d22 internal test value activation
Test operation
Normal operation
Continuous light
Dark
Flashing light (flashing rate 0,2s)
Flashing light (flashing rate 1s)
C−E disabled, max. perm. voltage: 48 V
C−E conducting, max. perm. current: 100 mA
LOW: 0 ... +3 V, HIGH: +13 ... +48 V
input LOW = disable of channel supervision and alarm
output
input HIGH or open = channel supervision and alarm
output is enabled
input LOW
input HIGH or open
input LOW
input HIGH or open