Herunterladen Inhalt Inhalt Diese Seite drucken

AFRISO Europress Betriebsanleitung Seite 74

Überdruck-leckanzeigegerät
Vorschau ausblenden Andere Handbücher für Europress:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
4.7
Technical data
Parameter
General specifications
Weight
Emission/alarm sound
Additional connections
Breaking capacity output
relay
Relay fuse
Operating pressure in
interstitial space
Switching point Alarm On 470 ± 10 mbar
Switching point Alarm Off 500 ± 10 mbar
Switching point Pump On 500 ± 10 mbar
Switching point Pump Off 530 ± 10 mbar
Safety valve opens
Hose line standard
Length of hose line
Operating temperature range
Ambient
Outdoor installation with
protective housing and
heating
Storage
Supply voltage
Nominal voltage
Nominal power
Product description
Value
1.2 kg
Min. 70 dB(A)
A-weighted sound level of the audible alarm at
a distance of one metre.
1 output relay (changeover contact)
Max. 250 V, 2 A, resistive load
T 2 A
standard version
Approx. 510 mbar
≥ 570 mbar
PVC hose 6 x 2 mm
Max. 50 m
-5/+60 °C
-25/+60 °C
-25/+60 °C
AC 100 - 240 V ±10 %
< 10 VA
Special version
See nameplate on prod-
uct.
Europress
EN
16

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis