Super Digital Inverter

Serial installation in front and rear

Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the unit
should be lower than the height of the outdoor unit.

Standard installation

1,000 or
300 or
more
more

Installation of Outdoor Unit

Before installation, check the strength and horizontalness
of the base so that abnormal sounds do not emanate.
According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
Drain nipple
mounting hole
As shown in the figure below, install the foundation and
vibration-proof rubber pads to directly support the bottom
surface of the fixing leg that is in contact with and
underneath the bottom plate of the outdoor unit.
*
When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
Fixing leg
Foundation
Foundation
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
EN
1,500 or
2,000 or
more
more
Drain hole
525
150
600
Drain hole
GOOD
with vibration-proof
GOOD
outdoor unit.
If only the end of the
fixing leg is supported, it
Set the out margin of the anchor bolt to 15 mm or less.
200 or
more
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof rubber
cap, and use the drain hose (Inner diam: 16 mm) sold on
the market. Also seal the knockout hole and screws
securely with silicone material, etc., to prevent water from
leaking.
Some conditions may cause dewing or dripping of water.
When collectively draining discharged water completely,
use a drain pan.
150
For Reference
Absorb vibration
If a heating operation is to be continuously performed for a
rubber pads
long time under the condition that the outdoor temperature is
0 °C or lower, draining defrosted water may be difficult due to
the bottom plate freezing, resulting in trouble with the cabinet
or fan.
It is recommended to procure an anti-freeze heater locally in
order to safely install the air conditioner.
For details, contact the dealer.
Bottom plate of
outdoor unit
9
NO GOOD
may deform.
Foundation
Drain nipple
Knockout hole
Do not support the
outdoor unit only with
the fixing leg.
15 or less
Waterproof rubber cap
(5pcs.)
Drain nipple
Waterproof rubber cap