Airwell DID Installationsanweisung Seite 21

Kanal- klimagerät mit elektronischer steuerung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 24
4. After 6 minutes, the air conditioning unit stops operating once automatic airflow
adjustment has finished.
CAUTION !!
• DO NOT adjust the dampers when automatic airflow adjustment is active.
• If there is no air flow change after automatic airflow adjustment, try to reset once more
again before contacting the dealer.
• If the duct or indoor unit location have been changed or outdoor is replaced, it is
necessary to perform the air flow automatic adjustment as described in the procedure
above.
USING THE WIRE CONTROLLER TO SET AIRFLOW RATE LEVEL
For RCW06
When the air conditioning unit is off, perform the following steps:
- Press "COPY" button
- Press "+" or "-" to select the SP.
- Press "CONFIRM" to P set the airflow rate in the range of 0~4.
- Press "ON/OFF" to finish the airflow setting.
"0": No airflow change
"1"~"4":Airflow increase progressively
For RCW08
When the air conditioning unit is off, perform the following steps:
- Press "MODE" and "FAN" for three seconds.
- Press "△" or "▽" to select the SP.
- Press "MODE" to set the airflow rate in the range of 0~4.
- Press "ON/OFF" to finish the airflow setting.
"0": No airflow change
"1"~"4":Airflow increase progressively
21