Functions and features
• The controller integrates 1 or 2 AS-i masters, a mini controller and a
Profibus-DP interface.
• it controls the data exchange to the sensor/actuator level
• it processes the peripheral data in the integrated processor (signal
preprocessing)
• it works as stand-alone controller with data exchange to the PC
(visualisation).
• it communicates with the higher-level control system (in the gate-
way mode)
Programming interface RS232C
• baud rate 4800 to 62400 baud
• max. distance between controller and host: 20m
• no potential separation from the controller supply
• pin connections: pin2: Rxd; pin 3: Txd; pin 5: Gnd
Programming interface Profibus-DP
• baud rate 9600 to 12Mbaud
• max. distance between controller and host: depending on the baud
rate
• potential separation from the controller supply
• up to 31 controllers connected in parallel
• pin connections: pin3: signal B; pin 8: signal A

Mounting

Mount the controller onto a 35mm rail. The unit has protection IP20,
therefore it should be mounted in a protected place (e.g. switching
cabinet).
Ensure a condensation-free environment. Avoid excessive dust,
vibration and shock. The circulation of air through the vents
must not be hampered.