• Constant curve.
The external analog signal will control the pump curve within the range
from the min. curve to the constant curve selected according to the char-
acteristic in fig. 2.
• Proportional-pressure or constant-pressure control.
The external analog signal will control the setpoint for the pump head be-
tween the setpoint corresponding to the min. curve and the setpoint se-
lected according to the characteristic in fig. 2.
At an input voltage lower than 0.5 V, the pump will operate according to the
min. curve. The setpoint cannot be changed.
The setpoint can only be changed when the input voltage is higher than
0.5 V.
Fig. 2
Max. setpoint/constant curve
H
m
H
set
Min. curve
0
1
2
Note:
• The max. curve input must be open.
• The min. curve input must be closed.
See connection examples on pages 86 and 87.
The examples below illustrate the use of an analog control voltage in con-
nection with a pump in constant-pressure control mode:
Fig. 3
H
set
Note: As will appear from the above figure, the control range will be reduced
if the setpoint of the pump, H
set
66
Setpoint set/constant curve
3
4
5
6
7
8
9
10
U
V
U
V
10
8,6
7,2
H
5,8
set
4,3
3,0
1,5
0,5
0
, is set to a lower value.